A---3
Appendix
Frequency of Sources
DIP switch actuator 7 selects either 50 or 60 Hz source
frequency. See Table C.
Table C. Source Frequency — DIP actuator 7.
DIP
switch
actuator
50 Hz
60 Hz
7
Phases of Normal & Emergency Sources
DIP switch actuators 8 and 9 select either 1 phase or 3
phase for the Normal and Emergency sources. See
Tables D and E.
Table D. Normal Source Phases — DIP actuator 8.
DIP
switch
actuator
1 Phase
3 Phase
8
Table E. Emergency S. Phases — DIP actuator 9.
DIP
switch
actuator
1 Phase
3 Phase
9
Data Input Lock
The Group 5 controller has an external input for a dry
contact that, if closed, prevents setting changes from
the keypad. DIP switch actuator 10 selects either yes
or no for the external input (such as a key switch).
Placing DIP switch actuator 10 in the Yes position
enables the controller to respond to the external input.
See Table F.
Lost or Forgotten Password
Moving DIP switch actuator 10 to the Yes position will
allow a new password to be input (as long as the
external input is open). Once the new password has
been entered, return DIP switch actuator 10 to the No
position. See Table F.
Table F. Lock Input — DIP actuator 10.
DIP
switch
actuator
Yes
No
10