Temco DV1000/1200/1400 Series
76657
8.  To finish connections, place a small bead of silicone 
to the outside of the fireplace inlet flange. Then, slide 
the extension collar over the inlet flange and secure 
with the three (3) screws provided.  
NOTE:  We recommend driving in two (2) sheet metal 
screws at 180° adjacent to the gear clamp at each joint.
Flex Vent Through the Roof
(Vertical) Applications
All models are approved for:
1.  Vertical venting up to 35’ (10.7 m) with 7” x 4” flex.
2.  Multiple bends allowed. See section on General 
Venting.
3.  With each vertical installation, a VSK7MH-2 kit may 
be used.   
T190
ceiling install
12/5/03 djt
Room Above 
Ceiling Level
Ceiling Joist
Firestop
T190
Fig. 23  Firestop at ceiling level.
T190
ceiling install
12/5/03 djt
Firestop
Attic Above Ceiling 
(Uninsulated)
Attic Above Ceiling 
(Insulated)
Attic Insulation 
Shield
T190
Fig. 24  Attic insulation shield.
6' (1.8m)
Maximum
35' (10.7m)
Maximum
T191
thru the roof
installation
12/5/03  djt
Roof
Attic Insulation 
Shield
7” (178 mm) Dia.
Joists
T191
Fig. 25   Typical through-the-roof installation.
The VSK7 Kit contains:
•  Vertical Termination Cap and Storm Collar
•  4”/7” dia. x 24” Rigid Pipe (unitized)
•  7” dia. Roof Support Components
•  0/12-5/12 Flashing with Storm Collar
•  Tube High Temp Sealant
•   7” dia. Inlet Ext. Collar
•  Firestop
•  Hardware Pack
•  Instruction
VSK7 Vertical Flex Vent Kit Installation
1.  Locate the fireplace.
2.  Mark ceiling above unit where flex will come through.
 *-REFER TO VERTICAL TERMINATION LOCATION 
CHART
3.  Ceiling opening should be a minimum of 9¹⁄₂” x 9¹⁄₂” 
(241 x 241 mm) and framed to that size.
4.  Mark opening in roof and cut a hole minimum 9¹⁄₂” x 
9¹⁄₂” (241 x 241 mm) and frame to that size.
5.  Place fireplace in proper location and secure to the 
floor.
6.  Install the firestop at the ceiling level.
7.  If an attic space (insulated or not) is located above 
the ceiling, the firestop should be installed to the 
underside of the ceiling. The firestop maintains the 
proper air-space clearance from the vent to insula-