temco-tool dv1000n-p Manuel D’Utilisation

Page de 40
6
Temco DV1000/1200/1400 Series
76657
X
T175
rough opening
depth
vertical vent
12/3/03  djt
1” (25 mm) 
Minimum Air Space 
Clearance to Com-
bustible Materials
   
Vent 
 
“X”
   System Used 
DV1000  DV1200  DV1400
  TEMCO 4/7 Flex 
17¹⁄₂” 
18¹⁄₂” 
19¹⁄₂” 
   
 
(445 mm)  (470 mm)  (495 mm)
  TEMCO 4/7 Rigid 
18¹⁄₂” 
19¹⁄₂” 
19¹⁄₂” 
   
 
(470 mm)  (495 mm)  (495 mm)
  Duravent 4/6-5/8 GS 
17¹⁄₂” 
18¹⁄₂” 
18¹⁄₂” 
   
 
(445 mm)  (470 mm)  (470 mm)
T175
Fig. 3  Minimum framing depths with vertical takeoff.
A
B
C
10³⁄₄"
(273mm)
Min.
D
T176
rough opening
depth horizontal
12/3/03  djt
  Model 
D
  DV1000  15³⁄₈” Min. 
30¹⁄₈” 
25³⁄₈” 
36¹⁄₈” 
 
 
(391mm)  (765mm)  (645mm)  (918mm)
  DV1200  16¹⁄₂” Min. 
34³⁄₄” 
30” 
40³⁄₄” 
 
 
(419mm)  (883mm)  (762mm) (1035mm)
  DV1400  16¹⁄₂” Min. 
40³⁄₄” 
36” 
46³⁄₄” 
 
 
(419mm)  (1035mm)  (914mm) (1188mm)
Firestop/Wall Sleeve
Combustible 
Construction 
Allowed
VEF (Vinyl Siding) 
or BEF (Brick) 
Extension flange
Vent Terminal
Standoff
T176
2 x 4 or 2 x 6 Framing
Fig. 4  Minimum framing dimensions with horizontal venting.
Framing and Finishing
1.  Choose a fireplace location and frame in accordance 
with the fireplace dimensions specified on Page 3 of 
this manual. When using a surround, the fireplace 
must be flush to the wall. Also, allowances must 
be made for drywall, tile or any other facing used 
around the unit.
2.  When the appliance is installed directly on carpeting, 
tile or other combustible material other than wood 
flooring, the appliance shall be installed on a metal 
or wood platform.
3.  Pull out the nail tabs which are located on each side 
of the fireplace. Move the fireplace into position and 
secure to the floor with screws or nails through the 
holes provided in the bottom flanges of the side cas-
ing. After checking unit for squareness, secure top of 
fireplace to the framing with screws or nails using the 
nailing tabs provided.
4.  Cold climate installation recommendation:  when 
installing this fireplace against a non-insulated exte-
rior wall or chase, it is recommended that the outer 
walls be insulated to conform to applicable insulation 
codes. Drywall should be installed around the unit to 
prevent insulation from contacting the body.
  Note:  Never let vapor barrier contact the outer 
case of this fireplace or venting.
Locating Your Fireplace
Y
E
A
B
C
D
F
Y
B
X
LU584-T
Locating unit
12/18/02  djt
X
LU584-1
Fig. 2  Locate gas fireplace.
A)  Flat on wall 
B)  Cross Corner 
C)  As an Island
D)  As a room divider  E)  Flat on wall corner  F)  Exterior wall
Island installation is possible as long as the horizontal portion of the 
vent system does not exceed maximum recommended horizontal run 
as outlined in the venting chart on Page 10.  When you install your 
fireplace as in position ‘B’, ‘D’ or ‘E’, (Fig. 2) a minimum of 1” (25mm) 
clearance must be maintained from the perpendicular wall and the 
front of the appliance.