The EB-1 Electrical junction box has been fitted stand-
ard on this model to allow for the easy connection of an 
optional fan kit. 
To connect the EB-1 box to the house electrical supply 
follow the steps below.
1.  Unscrew retaining screw from EB-1 base plate  (Fig. 
8) and remove the EB-1 assembly from the appli-
ance. 
2.  Remove the front cover of the EB box.
3.  Remove the plug socket assembly from the EB-1 
box.
4.  Feed the supply line in through the EB-1 opening in 
the side of the appliance and then through the back 
of the EB-1 assembly. (Fig. 8)
5.  Connect the black wire of the power supply line to 
the brass screw (polarized) of the socket assembly.
6.  Connect the white wire of the power line to the 
chrome screw of the socket assembly.
7.  Connect the ground wire of the supply line to the 
green screw of the socket assembly.
8.  Refit the socket assembly back into the electrical 
box and replace the cover plate. Secure the cable 
with the clamp on the outside of the EB-1 base 
plate and refit the EB-1 assembly to the unit with the 
screw removed in step 1.
EB-1 Electrical Box
It is strongly suggested that the wiring of 
the EB-1 Electrical Junction Box be carried 
out by a licensed electrician.
Ensure that the power to the supply line 
has been disconnected before commenc-
ing this procedure.                
FP580
INSTA VENT FREE
EB1 JUNCTION BOX
11/18/97
OUTSIDE
FRONT OF UNIT
INSIDE
FRONT OF
 UNIT
Electrical Box
Retaining Screw
FP580
Fig. 8  EB-1 receptacle.
Do not wire the remote ON/OFF wall 
switch for the gas fireplace to the 120  volt 
power supply.
Alternate Switch Location
The remote switch can be installed on the front/side of 
the access door. Simply mount the switch to the bracket 
provided and screw the bracket to either side of the 
frame, lining up the screws with the pre-punched holes.  
(Fig. 7)
TP
TH
TP
TH
FP1224
Remote switch
11/02
Remote ON/OFF 
Switch or Thermostat or 
Remote Control
Gas 
Control 
Valve
FP1224
Fig. 6  Remote switch wiring diagram.
T256
alternate
remote switch
location
5/10/04   djt
T256
Fig. 7  Alternate switch location.
The fireplace, when installed, must be 
electrically connected and grounded in 
accordance with local codes or, in the ab-
sence of local codes, with the current CSA 
C22.1 Canadian Electrical Code.
For USA installations follow local codes 
and the national electrical code  ANSI/
NFPA No. 70.