Basic 32 Loader Control UGC007/0702
D-8 Fault Messages and Error Codes
xx8B
(1)(2)
EXPANSION I/O
POWER SUPPLY
CONFIGURATION
MISMATCH ERROR
POWER SUPPLY
CONFIGURATION
MISMATCH ERROR
•
Either an expansion I/O power
supply is configured in the user
program, but no power supply is
present, or
supply is configured in the user
program, but no power supply is
present, or
•
an expansion I/O power supply is
configured in the user program
and a power supply is physically
present, but the types do not
match.
configured in the user program
and a power supply is physically
present, but the types do not
match.
Non-User
•
Correct the user program to eliminate a
power supply that is not present
power supply that is not present
•
Re-compile, reload the program and enter
the Run mode, or
the Run mode, or
•
With power removed, add the missing
power supply.
power supply.
xx8C
(1)(2)
EXPANSION I/O
OBJECT TYPE
MISMATCH
OBJECT TYPE
MISMATCH
An expansion I/O object (i.e. cable,
power supply, or module) in the user
program I/O configuration is not the
same object type as is physically
present.
power supply, or module) in the user
program I/O configuration is not the
same object type as is physically
present.
Non-User
•
Correct the user program I/O configuration
so that the object types match the actual
configuration, and
so that the object types match the actual
configuration, and
•
Re-compile, reload the program and enter
the Run mode. Or
the Run mode. Or
•
Correct the actual configuration to match
the user program I/O configuration.
the user program I/O configuration.
•
Cycle power.
0x1F39
INVALID STRING
LENGTH
LENGTH
(3)
The first word of string data contains
a negative, zero, or value greater
than 82.
a negative, zero, or value greater
than 82.
Recoverable
Check the first word of the string data
element for invalid values and correct the
data.
element for invalid values and correct the
data.
(1) xx indicates module number. If xx = 0, problem cannot be traced to a specific module.
(2) The xx in this error code means that the error occurs at the location of the last properly configured Expansion I/O module +1. You should use this information in conjunction
with the specific error code to determine the source of the problem.
(3) Applies to MicroLogix 1500 1764-LSP Series B and 1764-LRP Processors.
Error
Code
(Hex)
Code
(Hex)
Advisory Message
Description
Fault
Classification
Classification
Recommended Action