Basic 32 Loader Control    UGC007/0702
D-8        Fault Messages and Error Codes
xx8B
(1)(2)
EXPANSION I/O 
POWER SUPPLY 
CONFIGURATION 
MISMATCH ERROR
Either an expansion I/O power 
supply is configured in the user 
program, but no power supply is 
present, or
an expansion I/O power supply is 
configured in the user program 
and a power supply is physically 
present, but the types do not 
match.
Non-User
Correct the user program to eliminate a 
power supply that is not present
Re-compile, reload the program and enter 
the Run mode, or
With power removed, add the missing 
power supply.
xx8C
(1)(2)
EXPANSION I/O 
OBJECT TYPE 
MISMATCH
An expansion I/O object (i.e. cable, 
power supply, or module) in the user 
program I/O configuration is not the 
same object type as is physically 
present.
Non-User
Correct the user program I/O configuration 
so that the object types match the actual 
configuration, and
Re-compile, reload the program and enter 
the Run mode. Or
Correct the actual configuration to match 
the user program I/O configuration.
Cycle power.
0x1F39
INVALID STRING 
LENGTH
(3)
The first word of string data contains 
a negative, zero, or value greater 
than 82.
Recoverable
Check the first word of the string data 
element for invalid values and correct the 
data.
(1)  xx indicates module number. If xx = 0, problem cannot be traced to a specific module.
(2) The xx in this error code means that the error occurs at the location of the last properly configured Expansion I/O module +1. You should use this information in conjunction 
with the specific error code to determine the source of the problem.
(3) Applies to MicroLogix 1500 1764-LSP Series B and 1764-LRP Processors.
Error 
Code 
(Hex)
Advisory Message
Description
Fault 
Classification
Recommended Action