Installing the Module
Caution
Refer to the Read Me First: Safety and Radio-Frequency Interference document 
before removing equipment covers or connecting/disconnecting any signal wires
A blue label stripe identifies the SCC-AIXX as an analog input module. 
The label also displays the icon shown in Figure 1-1.
 
Figure 1-1.  SCC-AIXX Icon
You can plug the SCC-AIXX into any analog input socket on the SC-2345. 
The socket you choose determines which E Series DAQ device channels 
receive the SCC-AIXX signals.
For single-stage input conditioning, plug the SCC-AIXX into any socket 
J(X
+1), where X is 0 to 7, and connect the input signals to the module as 
described in the 
 section.
If you use the SCC-AIXX in a dual-stage configuration, the SCC-AIXX 
must be the first-stage module. Plug it into any socket J(X
+9) and plug the 
second-stage SCC into socket J(X
+1), where X is 0 to 7. Connect the input 
signals to the SCC-AIXX as described in the 
section. The SC-2345 connects the output signals of the first-stage SCC to 
the inputs of the second-stage SCC. An example of dual-stage conditioning 
is an SCC-AI02 followed by an SCC-FV01 frequency input module.