venting installation
Continued
10 FooT RUle
All flue gas outlet chimney terminations must extend 
a minimum of 3 feet in height above the highest point 
where it passes through the roof and must be at least 
2 feet above the highest point of the roof that is within 
a horizontal distance of 10 feet (see Figure 25).
FInIsHInG FIRePlaCe
Combustible  materials,  such  as  wallboard,  gypsum 
board,  sheet  rock,  drywall,  plywood,  etc.  may  not 
make direct contact with sides and top around the fire-
place face. See clearance requirements in Figures 8 
and 9 on page 9. It is important that combustible ma-
terials do not overlap the face itself. Brick, glass, tile or 
other noncombustible materials may overlap the front 
face provided they do not obstruct essential openings. 
When overlapping with a noncombustible facing ma-
terial, use only noncombustible mortar or adhesive.
MasonRY (PReCasT) CHIMneY
Masonry  Chimney  may  be  used  instead  of  the  FMI 
Chimney  System.  Parts  come  in  14"  Diameter  and 
can be obtained by FMI PRODUCTS, LLC. See Ac-
cessories on page 35.
24" Min.
24" Min.
18" 
Min.
Typ.
Figure 24 - Multiple Chase Installation
10'
2' Min.
10'
3' Min.
2' Min.
3' Min.
Level of 
Flue Gas 
Outlet
Figure 25 - 10 Foot Rule
optional gas line installation
You may elect to add a vented decorative gas appli-
ance (gas log) to your Grand Meridian Fireplace. If 
so, follow the installation instructions from the Deco-
rative Gas Appliance manufacturer. Familiarize your-
self with requirements for installation as outlined by 
the National Fuel Gas Code, ANSI Z223.1/NFPA 54. 
This  gas  pipe  provision  should  only  be  used  on  a 
decorative gas appliance.
You can route the gas piping practically anywhere in 
the firebox – the floor, back wall or side walls. You 
will just need a masonry drill; the instructions from 
the gas appliance manufacturer will be very straight-
forward.
Fill in the holes you have drilled around the gas pip-
ing with the regular mortar.
Follow the Gas Log manufacturer’s instructions.
optional electrical connection installation
Like  the  gas  line,  electrical  feed  lines  can  be  run 
through  the  floor,  back  wall,  or  side  walls.  Follow 
local building and electrical code requirements.