FMI masonry firebox mm44 Manuel D’Utilisation

Page de 44
www.fmiproducts.com
125160-01A
20
1/2" Thick Cement Board Dimensions
Model
A1
A2
B1
B2
MM63
67"
28"
60"
23"
supporting Floor systems installation
Continued
Figure 29 - Anchorage Dimensions
Figure 30 - Hardware
Figure 31 - Typical Anchorage Layout
combustible Floor installation
8" MeTal Base (MMB63)
The  Metal  Base  (MMB63)  ensures  the  minimum 
8"  clearance  above  combustible  flooring  is  main-
tained with Grand Meridian Model MM63.
A layer of 1/2" minimum Cement Board (Not Includ-
ed) is required on the top and mid section below as 
shown in Figure 32, page 21. The required sizes are 
shown in the table below.
IMPORTANT:
 
Remember  to  tighten  up  nuts  below 
the floor after fireplace installation in order to take up 
any slack in the threads.
eMBeR PRoTeCToR sTRIPs:
Ember protector strips (included with Metal Base Kit) 
are required between the front of the Fireplace Hearth 
and  Hearth  Extension. A  minimum  thickness  of  26 
gauge metal strip at least 4" wide can be used. The 
length needs to extend 2 inches beyond each side 
of the fireplace opening. If two strips are used, make 
sure they overlap at least two inches in the middle. 
The strip is placed about 2" into the underside of the 
platform at the front (Figure 10, page 10).
NOTE: When using an on-site constructed hearth ex-
tension, you may use a sand-cement grout between 
the hearth and extension instead.
F
10"
4"
a
Model
a
MM33
32 ¾"
MM39
38 ¾"
MM44
43 ¾"
MM49
48 ¾"
MM63
62 ¾"
 
2” min 
clearance
Fireplace 
outline
10”
exaMPle onlY
seCTIon VIeW
RoTaTed 90CW