FMI flame-max fvfm27nr Manuel D’Utilisation

Page de 36
www.fmiproducts.com
121353-01H
7
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have 
a confined or unconfined space.
Space:  Includes  the  room  in  which  you  will 
install  heater  plus  any  adjoining  rooms  with 
doorless  passageways  or  ventilation  grills 
between the rooms.
1.  Determine the volume of the space (length 
x width x height).
 
Length x Width x Height = __________ c u . 
ft. (volume of space)
 
Example: Space size 20 ft. (length) x 16 ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)
 
If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example: 2560 cu. ft. (volume of space) x 20 
=  51,200  (maximum  Btu/Hr  the  space  can 
support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free heater 
_________Btu/Hr
 
Gas water heater* 
_________Btu/Hr
 
Gas furnace 
_________Btu/Hr
 
Vented gas heater 
_________Btu/Hr
 
Gas fireplace logs 
_________Btu/Hr
 
Other gas appliances*  +_________Btu/Hr
 
Total 
=_________Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.
 
Example:
 
Gas water heater* 
 __________ Btu/Hr
 
Vent-free heater 
+ _________ Btu/Hr
 
Total 
= _________ Btu/Hr
4.  Compare  the  maximum  Btu/Hr  the  space 
can support with the actual amount of Btu/Hr 
used.
 
  ______ Btu/Hr  (maximum  the  space  can 
support)
 
  ______ Btu/Hr  (actual  amount  of  Btu/Hr 
used)
40,000
33,000
73,000
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support)
 
73,000  Btu/Hr  (actual  amount  of  Btu/Hr 
used)
The space in this example is a confined space 
because the actual Btu/Hr used is more than the 
maximum  Btu/Hr  the  space  can  support.  You 
must  provide  additional  fresh  air. Your  options 
are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides an 
unconfined space, remove door to adjoining 
room or add ventilation grills between rooms. 
See Ventilation Air From Inside Building.
B.  Vent  room  directly  to  the  outdoors.  See 
Ventilation Air From Outdoors, page 8.
C.  Install a lower Btu/Hr heater, if lower Btu/Hr 
size makes room unconfined.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is 
an unconfined space. You will need no additional 
fresh air ventilation.
 WARNING: If the area in which 
the heater may be operated does 
not meet the required volume for 
indoor combustion air, combus-
tion and ventilation air shall be 
provided by one of the methods 
described  in  the  National  Fuel 
Gas Code, ANSI Z223.1/NFPA 54, 
the International Fuel Gas Code, 
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two  permanent  openings:  one  within  12"  of 
the  ceiling  and  one  within  12"  of  the  floor 
on the wall connecting the two spaces (see 
options 1 and 2, Figure 2, page 8). You can 
also  remove  door  into  adjoining  room  (see 
option 3, Figure 2). Follow the National Fuel 
Gas  Code,  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation
 for required size 
of ventilation grills or ducts.
AIR FOR COMbUSTION AND VENTILATION
Continued