Figure 2-17 shows the timing requirements on the SERCLK and 
SERDATIN signals. You must observe these timing requirements for all 
communications. T
delay
 is a specification of the SCXI-1121.
Figure 2-17.  Serial Data Timing Diagram
After the Slot-Select line to an SCXI-1121 has been asserted, you can write 
to its Configuration Register and read from its Module ID Register by 
following the protocols given below. The contents of the Module ID 
Register are reinitialized by deasserting Slot-Select. After the 32 bits of 
data are read from the Module ID Register, further data will be zeros until 
reinitialization occurs.
To write to the Configuration Register, follow these steps:
1.
Initial conditions:
SS* asserted low
SERDATIN = don't care
DAQD*/A = 0 (indicates data will be written to Configuration 
Register)
SLOT0SEL* = 1
SERCLK = 1 (and has not transitioned since SS* went low)
2.
For each bit to be written: 
Establish the desired SERDATIN level corresponding to this bit.
SERCLK = 0
SERCLK = 1. Clock the data.
T
low
T
high
SERCLK
SERDATIN
SERDATOUT
T
setup
T
hold
T
delay
T
low
Minimum low time
65 nsec minimum
T
high
Minimum high time
400 nsec minimum
T
setup
 
SERDATIN setup time 
200 nsec minimum
T
hold
SERDATIN hold time
200 nsec minimum
T
delay
SERDATOUT delay
350 nsec maximum