eWON Flexy Modular Remote Access (C1D2) Guide De Spécification

Page de 5
Flexy Serie100/200
Flexy are available in two series. The Serie 100 doesn’t provide routing 
capability between the LAN and the WAN interface and the Ethernet 
to serial gateway. The Flexy Serie 100 has been designed for Remote 
Data Collection application. The Serie 200 provides full features
Ethernet to Serial Gateways
MODBUS TCP to MODBUS RTU; XIP to UNITELWAY; EtherNet/IP™ to DF1; FINS 
TCP to FINS Hostlink; ISO TCP to PPI, MPI (S7) or PROFIBUS (S7); VCOM to ASCII. 
(Applicable to the serie 200)
Data Acquisition Protocols
MODBUS/RTU, MODBUS/TCP, Unitelway, DF1, PPI, MPI (S7), PROFIBUS (S7), 
FINS Hostlink, FINS TCP, EtherNet/IP™, ISO TCP, Mitsubishi FX, Hitachi EH, 
ASCII. Stored in 2500 internal tags
Alarms
Alarms notification by email, SMS, FTP put and/or SNMP traps.
4 Thresholds : low, lowlow, high, highhigh + deadband and activation 
delay.
Alarm logs in http and via FTP, Alarm cycle: ALM, RTN, ACK and END
Datalogging
Internal data base for data logging (real-time logging and historical 
logging up to 1,000,000 timestamps). Retrieval of the database with files 
transferred by FTP or email
SD card reader
yes, for Ordinary Location
Router
IP filtering, IP forwarding, NAT, Port forwarding, Proxy, Routing table, DHCP 
client. (Applicable to the serie 200)
VPN Tunnelling
Open VPN 2.0 either in SSL UDP or HTTPS
VPN Security
The VPN security model is based on using SSL/TLS for session 
authentication and the IPSec ESP protocol for secure tunnel transport 
over UDP. It supports the X509 PKI (public key infrastructure) for 
session authentication, the TLS protocol for key exchange, the 
cipher-independent EVP (DES, 3DES, AES, BF) interface for encrypting 
tunnel data, and the HMAC-SHA1 algorithm for authenticating tunnel 
data.
Programmable
Script interpreter for Basic language, embedded Java 2 Micro Edition 
environment
Synchronization
Embedded real-time clock, manual setup via http or automatic via NTP
File Management
FTP client and server for configuration, firmware update and data transfer
Website
Embedded web interface with setup wizards for configuration and 
maintenance (no extra software needed). Basic authentication 
(login/password) and session control for security. 
Possibility of uploading custom web GUI. Compatible with viewON3 
web HMI.
User Flash Disk
up to 30MB available for user application
Maintenance
SNMP V1 with MIB2 and/or via FTP files
Mechanicals
Din Rail Mounting
Dimensions: 80 x 89 x 134  mm (H x D x W ); 
Weight: < 500 g
Power supply
12 - 24VDC +/-20%, LPS
Consumption: depending on the extension card installed (see 
Installation guide on our website)
Input/output
2x digital input: 0 to 12/24VDC; 1.5kV isolation
1x digital output: open drain (MOSFET) 200mA; 1.5 kV isolation
FLEXY BASE  MODULE