Puls UBC10.241 DIN-Rail UPS Guide De Spécification

Page de 23
 
 
 
UBC10.241, UBC10.241-N1 
 
  USeries 
24V, 10A, DC-UPS 
 
 
May. 2008 / Rev. 1.1  DS-UBC10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
16/23 
 
20.  S
AFETY
 
 
  Output voltage  
SELV 
IEC/EN 60950-1  
   
PELV 
EN 60204-1, EN 50178, IEC 60364-4-41 
   
Max. allowed voltage between any input, output or signal pin and ground:  
60Vdc or 42.4Vac 
  Class of protection 
II 
PE (Protective Earth) connection is not required 
  Isolation resistance 
> 5MOhm 
Power port to housing, 500Vdc  
  Dielectric strength 
500Vac 
Power port to signal port 
   
500Vac 
Power port / signal port to housing 
 
Touch current (leakage current) 
The leakage current which is produced by the DC-UPS itself depends on the input 
voltage ripple and need to be investigated in the final application. 
For a smooth DC input voltage, the produced leakage current is less than 100μA. 
 
21.  A
PPROVALS
 
 
 UL 
508 
IND. CONT. EQ.
18WM
 
LISTED   E198865   listed for use in U.S.A. (UL 508) and  
Canada (C22.2 No. 14-95) 
Industrial Control Equipment
 
 UL 
60950-1 
 
 
RECOGNIZED   E137006    recognized for the use in  
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950)  
Information Technology Equipment, Level 5  
 UL 
1604 
 
 
RECOGNIZED   E246877    recognized for use in U.S.A. (UL 1604) and 
Canada (C22.2 No. 213-M1987) 
Hazardous Location Class I Div 2 T4 Groups A,B,C,D and  
Class I Zone 2 Groups IIA, IIB and IIC 
   
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations as well as for Class I 
Zone 2 Groups IIA, IIB and IIC locations. Substitution of components may impair suitability for 
Class I Division 2 environment. Do not disconnect equipment unless power has been switched 
off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National 
Electrical Code, NFPA 70, and in accordance with other local or national codes. 
  CSA 
R
182790
C
US
 
CSA approval for Canada 
CAN/CSA C22.2 No 107-1; CAN/ CSA 60950-1-03; UL60950-1 
  IEC 60950-1 
 
IECEE
 
CB SCHEME 
CB Scheme,  
Information Technology Equipment 
 Marine 
 
GL
  
ABS
 
GL (Germanischer Lloyd) classified and ABS (American Bureau for 
Shipping) PDA for marine and offshore applications. 
Environmental category: A, EMC2 
 
22.  F
ULFILLED 
S
TANDARDS
 
 
  EN/IEC 60204-1 
Safety of Electrical Equipment of Machines 
  EN/IEC 61131 
Programmable Controllers 
  EN 50178, IEC 62103 
Electronic Equipment in Power Installations