Puls UBC10.241 DIN-Rail UPS Guide De Spécification

Page de 23
 
 
 
UBC10.241, UBC10.241-N1 
 
  USeries 
24V, 10A, DC-UPS 
 
 
May. 2008 / Rev. 1.1  DS-UBC10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
18/23 
 
25.  I
NSTALLATION 
N
OTES
 
 
Mounting: 
The power terminals shall be located on top of the unit. An appropriate electrical and fire end-product enclosure 
should be considered in the end use application.  
Do not install unit in airtight housings or cabinets. The site in which the unit is located must have sufficient 
ventilation acc. to EN50272-2. 
Cooling:  Convection cooled, no forced air cooling required. Do not obstruct air flow!  
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended 
when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance are 
recommended. 
Risk of electrical shock, fire, personal injury or death! 
Turn power off and disconnect battery fuse before working on the DC-UPS. Protect against inadvertent re-powering. 
Make sure the wiring is correct by following all local and national codes. Do not open, modify or repair the unit, 
except replacement of the battery. Use caution to prevent any foreign objects from entering into the housing. 
Do not use in wet locations or in areas where moisture or condensation can be expected. 
Service parts: 
The DC-UPS contains an integrated battery which must be changed on a periodic basis, see chapter 26 and. 28.1. 
The tripping of an internal fuse is caused by an internal fault. If damage or malfunctioning should occur during 
operation, immediately turn power off and send unit to the factory for inspection! For Troubleshooting see 28.4. 
Wiring and installation instructions: 
(1)  It is recommended to install the DC-UPS in a place where the integrated battery will not be heated up by 
adjacent equipment. The unit is equipped with a fuseholder and a 30A battery fuse type ATO
®
 257 030 
(Littelfuse). The battery fuse protects the wires between the battery and the DC-UPS. It also allows the 
disconnection of the battery from the DC-UPS which is recommended when working on the battery or DC-UPS. 
Disconnect battery fuse before connecting the battery.  
(2)   Connect the power supply to the input terminals of the DC-UPS.  
(3)  Connect the buffered load to the output terminals of the DC-UPS. The output is decoupled from the input 
allowing load circuits to be easily split into buffered and non buffered sections. Noncritical loads can be 
connected directly to the power supply and will not be buffered. The energy of the battery can then be used in 
the circuits which require buffering. 
(4)   Plug-in the fuse when the wiring is finished. 
 
 
Fig. 25-1   Typical wiring diagram 
 
 
24V 
unbuffered 
branch
 24V 
Power 
supply
+
-
N
L PE
DC-UPS 
UBC10.241
24V
IN
+
-
+
-
24V 
buffered 
branch
24V
OUT
Buffered 
load
+
-
Unbuffered 
load
+
-