Puls CD5.121 DC/DC Converter Guide De Spécification

Page de 21
 
 
CD5.121
 
 
CD-Series 
DC/DC Converter 12V, 8A 
 
22.4.  C
HARGING OF 
B
ATTERIES
 
The DC/DC converter can be used to charge lead-acid or maintenance free 12V VRLA batteries. 
Instructions for charging batteries: 
a) 
Ensure that the ambient temperature of the DC/DC converter is below 45°C 
b) 
Do not use DC/DC converters in mounting orientations other than the standard mounting orientation (input 
terminals on the bottom and output terminals on top of the unit). 
c) 
Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge 
voltage. 
End-of-charge voltage 
13.9V 13.75V 
13.6V 13.4V 
Battery 
temperature  10°C 20°C 30°C 40°C 
d) 
Use a 10A circuit breaker (or blocking diode) between the DC/DC converter and the battery. 
e) 
Ensure that the output current of the DC/DC converter is below the allowed charging current of the battery. 
f) 
The return current to the DC/DC converter (battery discharge current) is typ. 15mA when the DC/DC converter is 
switched off (except in case a blocking diode is utilized). 
22.5.  E
XTERNAL 
I
NPUT 
P
ROTECTION
 
The unit is tested and approved for branch circuits up to 50A. An external protection is only required, if the supplying 
branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local 
regulations might apply. 
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of 
the circuit breaker. A minimum value of 10A B- or 8A C-Characteristic breaker should be used. 
22.6.  R
EQUIREMENTS FOR THE 
S
UPPLYING 
S
OURCE
 
In certain circumstances, the input filter of the DC/DC converter can show a resonant effect which is caused by the 
supplying network. Especially when additional external input filters are utilized, a superimposed AC voltage can be 
generated on the input terminals of the DC/DC converter which might cause a malfunction of the unit. Therefore, 
additional input filters are not recommended. To avoid the resonant effects, the minimal resistance of the supplying 
network which depends on the inductance of the input network, shall be above the boundary curve in Fig. 22-3. 
 
 
Fig. 22-3   External input filter requirements to 
avoid filter instabilities 
 
1 mOhm
10 mOhm
100 mOhm
1 Ohm
0.1mH
1mH
10mH
Inductance of the supplying network
Resistance of the
supplying network
 (a) max.
 (b) typ.
(a)
(b)
Oct 2009 / Rev. 1.3  DS-CD5.121-EN 
All parameters are specified at 12V, 8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
18/21