Puls ML30.241 Power Supply Guide De Spécification

Page de 22
 
 
ML30.241
 
 
MiniLine 
 
24V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
6.  H
OLD
-
UP 
T
IME
 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Hold-up Time 
typ. 
41ms 
66ms 
285ms 
at 24V, 0.65A, see Fig. 6-1
 
typ. 
18ms 
31ms 
141ms 
at 24V, 1.3A, see Fig. 6-1
 
Note:  At no load, the hold-up time can be up to several seconds. The green DC-on lamp is also on during this time 
 
 
 
Fig. 6-1   Hold-up time vs. input voltage 
 
Fig. 6-2   Shut-down behavior, definitions 
 
0
20
40
100
120ms
85
120
155
190
230Vac
Input Voltage
Hold-up Time
60
80
a) 24V 0.65A typ.
b) 24V 0.65Amin.
c) 24V 1.3A typ.
d) 24V 1.3A min.
a
b
c
d
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
 
 
 
 
7.  DC-I
NPUT
 
The power supply can also be supplied from a DC source. Use a battery or similar DC source. For other sources contact 
PULS. Connect the + pole to L and the – pole to N. Connect the PE terminal to an earth wire or to the machine ground. 
 
DC input 
nom. 
DC 110-300V 
-20%/+25% 
DC input range 
min. 
88-375Vdc 
continuous operation, reduce output power according 
Fig. 7-2 at voltages below 110Vdc 
Allowed Voltage L/N to Earth 
max. 
375Vdc 
IEC 62103 
DC input current 
typ. 
0.31A / 0.12A 
110Vdc / 300Vdc, at 24V, 1.3A 
Turn-on voltage 
typ. 
60Vdc 
steady state value 
Shut-down voltage 
typ. 
35Vdc 
steady state value 
 
 
Fig. 7-1   Wiring for DC Input 
 
Fig. 7-2   Allowable output current below 
110Vdc input voltage 
 
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
 
 
0
5
10
15
20
30W
85
95
105
115
135Vdc
Input Voltage Vdc
Output Power
25
125
(a)
(b)
 (a) Ambient <60°C
 (b) Ambient <45°C
xxx. 201x / Rev. 1.0  DS-ML30.241-EN 
All parameters are specified at 24V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
7/22