Puls ML50.100 Power Supply Guide De Spécification
ML50.100, ML50.109
MiniLine
24V, 2.1A, S
INGLE
P
HASE
I
NPUT
Mar. 2007 / Rev. 1.0 DS-ML50.100-EN
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/20
19. S
AFETY
Input / output separation
SELV
IEC/EN 60950-1
PELV
EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
input to output, 500Vdc
Touch current (leakage current)
typ. 0.12mA
100Vac, 50Hz, TN mains
typ. 0.17mA
120Vac, 60Hz, TN mains
typ. 0.29mA
230Vac, 50Hz, TN mains
< 0.16mA
110Vac, 50Hz, TN mains
< 0.23mA
132Vac, 60Hz, TN mains
< 0.40mA
264Vac, 50Hz, TN mains
20. D
IELECTRIC
S
TRENGTH
Fig. 20-1 Dielectric strength
A B C
Type test
60s
2500Vac
3000Vac
500Vac
Factory test
5s
2500Vac
2500Vac
500Vac
Field test
5s
2000Vac
2000Vac
500Vac
A
C
N
L
Input
Earth, PE
B
Output
-
+
DC-
Ok
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect L and N together as well as all
output poles.
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect L and N together as well as all
output poles.
The output voltage is floating and has no ohmic connection to ground.
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, it is recommended that either the + pole, the – pole
or any other part of the output circuit should be connected to the protective earth system. This helps to avoid
situations in which a load starts unexpectedly or can not be switched off when an unnoticed earth faults occur.
or any other part of the output circuit should be connected to the protective earth system. This helps to avoid
situations in which a load starts unexpectedly or can not be switched off when an unnoticed earth faults occur.