Puls ML50.100 Power Supply Guia De Especificação

Página de 20
 
 
 
ML50.100, ML50.109 
 
MiniLine 
 
24V, 2.1A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
12/20 
19. S
AFETY
 
 
  Input / output separation  
SELV 
IEC/EN 60950-1  
   
PELV 
EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 
   
double or reinforced insulation 
  Class of protection 
PE (Protective Earth) connection required 
  Isolation resistance 
> 5MOhm 
input to output, 500Vdc  
  Touch current (leakage current) 
typ. 0.12mA 
100Vac, 50Hz, TN mains 
   
typ. 0.17mA 
120Vac, 60Hz, TN mains 
   
typ. 0.29mA 
230Vac, 50Hz, TN mains 
   
< 0.16mA 
110Vac, 50Hz, TN mains 
   
< 0.23mA 
132Vac, 60Hz, TN mains 
   
< 0.40mA 
264Vac, 50Hz, TN mains 
 
 
20. D
IELECTRIC 
S
TRENGTH
 
 
 
Fig. 20-1   Dielectric strength 
 
 
 
A B C 
Type test 
60s 
2500Vac 
3000Vac 
500Vac 
Factory test 
5s 
2500Vac 
2500Vac 
500Vac 
Field test 
5s 
2000Vac 
2000Vac 
500Vac 
 
A
C
N
L
Input
Earth, PE
B
Output
 -
+
DC-
Ok
 
 
Type tests and factory tests:  
Conducted by the manufacturer. Do not repeat test in field! 
Rules for field test: 
Use appropriate test equipment which applies the voltage 
with a slow ramp! Connect L and N together as well as all 
output poles. 
 
The output voltage is floating and has no ohmic connection to ground. 
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, it is recommended that either the + pole, the – pole 
or any other part of the output circuit should be connected to the protective earth system. This helps to avoid 
situations in which a load starts unexpectedly or can not be switched off when an unnoticed earth faults occur.