Puls CS3.241 Power Supply Guide De Spécification
CS3.241
C–Series
24V, 3.3A, S
INGLE
P
HASE
I
NPUT
September. 2007 / Rev. 1.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/21
13. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 13-1 Front side
Output voltage potentiometer
Open the flap to tune the output voltage.
Factory set: 24.1V
Open the flap to tune the output voltage.
Factory set: 24.1V
Output Terminals
Screw terminals
Screw terminals
+ Positive output
- Negative (return) output
Dual pins per pole
- Negative (return) output
Dual pins per pole
Input Terminals
Screw terminals
N … Neutral input
L … Line (hot) input
... PE (Protective Earth) input
DC-on lamp (green)
On when the voltage at the output
terminals is > 21 V
terminals is > 21 V
14. T
ERMINALS AND
W
IRING
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring.
other (input below, output above) to help in error-free wiring.
Type
Screw
terminals
Solid
wire
0.5-6mm
2
Stranded
wire
0.5-4mm
2
American wire gauge
20-10 AWG
Ferrules
Allowed, but not required
Wire stripping length
7mm / 0.275inch
Screwdriver
3.5mm
slotted or Pozidrive No 2
Recommended tightening torque
0.8Nm, 7lb.in
Instructions:
a)
Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b)
Follow national installation codes and installation regulations!
c)
Ensure that all strands of a stranded wire enter the terminal connection!
d)
Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e)
Do not use the unit without PE connection.
f)
In order to fulfill GL requirements, unused terminal spaces must be closed.