Puls CS3.241 Power Supply Guia De Especificação

Página de 21
 
 
 
CS3.241 
 
  CSeries 
24V, 3.3A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
September. 2007 / Rev. 1.1  DS-CS3.241-EN 
All parameters are specified at 24V, 3.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
9/21 
 
13. F
RONT 
S
IDE AND 
U
SER 
E
LEMENTS
 
 
Fig. 13-1   Front side
 
Output voltage potentiometer  
Open the flap to tune the output voltage. 
Factory set: 24.1V 
 
Output Terminals 
Screw terminals 
 
+          Positive output  
          Negative (return) output 
            Dual pins per pole  
 
 
 
 
 
 
 
 
 
 
 
Input Terminals 
Screw terminals 
N … Neutral input 
L …  Line (hot) input 
... PE (Protective Earth) input 
 
DC-on lamp (green) 
On when the voltage at the output 
terminals is > 21 V
 
 
 
 
14. T
ERMINALS AND 
W
IRING
 
 
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each 
other (input below, output above) to help in error-free wiring. 
 Type 
Screw 
terminals 
 Solid 
wire 
0.5-6mm
2
 
 Stranded 
wire 
0.5-4mm
2
 
  American wire gauge 
20-10 AWG 
  Ferrules 
Allowed, but not required  
  Wire stripping length 
7mm / 0.275inch 
 Screwdriver 
3.5mm 
slotted or Pozidrive No 2 
  Recommended tightening torque 
0.8Nm, 7lb.in 
 
Instructions: 
a) 
Use appropriate copper cables that are designed for an operating temperature of:  
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.  
b) 
Follow national installation codes and installation regulations! 
c) 
Ensure that all strands of a stranded wire enter the terminal connection!  
d) 
Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire). 
e) 
 Do not use the unit without PE connection. 
f) 
In order to fulfill GL requirements, unused terminal spaces must be closed.