Calculating Wire Ranges for RM4 Readers
From Table C-1, the RM4 Reader draws 75 mA (rounded up to 100 mA or .1 
A), as listed in 
From Table C-2, the resistance with 18 AWG wire is 0.00879 ohms per foot. 
From Figure C.1, the diagram shows that you are going to connect three 
RM4s to the apC/8X. The RM4/4Es are laid out as follows.
RM A is 50 ft. from the apC/8X 
RM B is 500 ft. from RM A.
RM C is 250 ft. from RM B.
Perform wire range calculations, as follows:
1. Calculate the voltage drop for each reader in the chain by multiplying 
the distance between each device by power (amps) by resistance (ohms 
per foot).
2. Add the voltage drop for each reader to get the total voltage drop.
3. Subtract the total voltage drop from the original apC/8X supply.
4. Is remaining voltage sufficient to operate the readers?