Deister Electronic GmbH PRD2SWH3000 Manuel D’Utilisation

Page de 16
6
WIRING
The SWH-3000 model has ten terminals as noted in Table 2. When 
attaching wires to the connector, strip off only the minimum insulation 
required (approx. 1/8'') and push the wire into the connector until the 
insulation is flush or inside the connector body. This is particularly critical 
for outdoor readers. While the reader itself is designed and protected to 
IP65 standards, the cable wires can potentially corrode and short together if 
not carefully mounted and tightly fastened in the connector body.
Table 3 indicates maximum wiring distances per Wiegand standard with 
the three most common gauges of cable.
TABLE 2.  Connector Pins for Model SWH-3000
Pin
Description
Pin
1
External Beeper Control
6
Reserved for Future Use
2
Ground
7
External Green LED Control
3
Power (8 to 16 VDC)
8
External Red LED Control
4
D1 Wiegand
9
No connection
5
D0 Wiegand
10
No connection
TABLE 3. Maximum cable distance for 18, 20, or 22 AWG wire
Wire Gauge
18 AWG
20AWG
22 AWG
Cable 
Distance
500 feet 
(152 meters)
300 feet
(91 meters)
200 feet
(61 meters)