18.8  Remote Arming/Disarming for Ademco Vista Control Panels
The following steps describe how to configure the CellComSL to arm and disarm an Ademco Vista control panel from
a schedule or remotely from the Virtual Keypad App, Virtual Keypad Browser, MyAccess™, or RemoteLink™, using the 
Remote Arming Output. See Figure 17: Ademco Vista 20P to CellComSL.
1.   Locate output 17 on the Ademco control panel (far left pin on the 7 pin header located in the middle of the PCB).
Connect output 17 to Zone 1 (Z1) on the CellComSL. Connect a 1k ohm EOL resistor from Zone 1 to ground (G).
2.   Connect Output 1 (O1) on the CellComSL to Zone 3 (terminal 12) on the Vista control panel.
3.  On the Vista control panel, enter programming by entering the Installer Code followed by 800. Press * and Field ?
displays.
4.   Program Zone 3 as an Arming Zone. Enter 56 and program the following:
 
a.  Set to Confirm? - Enter 0.
b.  Enter Zn Num. - Enter 03, press * to continue.
c.  Summary Screen: Zn ZT P RC HW:RT - Press * to continue.
d.  Zone Type - Enter 77, press * to continue.
e.  Report Code 1st 01 2nd 00 10 - Press * to continue.
f.  Hardware Type - Enter 0, press * to continue.
f.  Resp Time - Enter 1, press * to continue.
g.  Summary Screen: Zn ZT P RC HW:RT - Press * to continue.
h.  Program Alpha - Enter 0.
i.
Enter ZN Num displays, enter 00 to exit.
5.  Program Output 17. Enter * or # displays. Press * and Field? displays. Enter 79 and program the following:
 
a.  Enter Output No - Enter 17, press * to continue.
b.  Output Normally Low - Enter 0, press * to continue.
c.  Enter Output No displays. Enter 00 to exit.
6.   Define Output 17 actions. Enter * or # displays. Press * and Field? displays. Enter 80 and program the following:
 
a.  Program Output 17 to turn on when armed Stay. Output Funct# - Enter 01, press * to continue.
•   Summary Screen: 01 A E P Trig - Press * to continue.
•   Activated by: - Enter 2, press * to continue.
•   Enter Zn Type - Enter 20, press * to continue.
•   Output Action - Enter 2, press * to continue.
•   Enter Output No. - Enter 17, press * to continue.
•   Summary Screen: 01 A E P Trig - Press * to continue.
b.  Program Output 17 to turn on when armed Away. Output Funct# - Enter 02, press * to continue.
•   Summary Screen: 02 A E P Trig - Press * to continue.
•  Activated by: - Enter 2, press * to continue.
•   Enter Zn Type - Enter 21, press * to continue.
•   Output Action - Enter 2, press * to continue.
•   Enter Output No. - Enter 17, press * to continue.
•   Summary Screen: 02 A E P Trig - Press * to continue.
c.  Program Output 17 to turn off when Disarmed. Output Funct# - Enter 03, press * to continue.
•   Summary Screen: 03 A E P Trig - Press * to continue.
•  Activated by: - Enter 2, press * to continue.
•   Enter Zn Type - Enter 22, press * to continue.
•   Output Action - Enter 0, press * to continue.
•   Enter Output No. - Enter 17, press * to continue.
•   Summary Screen: 03 A E P Trig - Press * to continue.
d.  Output Funct# - Enter 00, press * to continue.
7.  Enter * or # displays. Press * and Field? displays. Enter 99 to exit programming.
8.  Programming the CellComSL.
 
a.  Reset the CellComSL. Enter 6653.
b.  Press CMD to Output Options. Press any select key (top row key).
c.  Program Output 1 in Remote Arming Output. Press CMD to RMT ARMG OUT:. Enter 1 CMD.
d.  Press CMD to Zone Information. Press any select key and Zone No. - displays.
e.  Enter 1, press CMD.
f.  Enter a zone name. Press CMD.
g.   Program Zone 1 as an Arming Zone. Zone Type: - displays. Choose Arming Zone type AR. Press CMD.
h.  Area: 1------ displays. Press CMD.
i.
Style: TOGGLE displays. Choose MNT.
j.  Exit Programming.