en | Installation and Setup
Security Escort Point Tracking Transmitter
2017.11 | SE3v1.0 | DL
Installation Manual
Robert Bosch (SEA) Pte Ltd
3.2.2
12 VDC input
1.
Set the jumper over the jumper pins as illustrated in the diagram below.
2.
Connect the 12 VDC source to the connector of the transmitter.
Figure 3.9: 12 VDC input
1 Jumper setting
2 12 VDC in
3.3
Setting up magnetic or external contacts
The SEC-3402 series has the capacity to monitor magnetic and/or dry external contacts.
External Normally Closed (NC) or external Normally Open (NO) contacts can be monitored.
Recommended cable: 18 AWG < 20 ft (6 m)
EOL resistor: 1 Mega ohms
Notice!
If not using external contacts, you must install the EOL resistor.