ON
1 2 3 4 5 6 7 8
128
64
32
16
8
4
2
1
ON
Turn to “ON” stand for ON
9 10
Function for Initializing
 Operation
Function for the intercom 
linkage 
  Turn to the “number”stand for OFF
   
Figure 2-1-2 The definition diagram of dial switch
 
Note:
 
1)  Binary  encoding  is  adopted  to  the  address.The  range  of 
machine  number  can  be  set  is  from1  to  255.  Eg:  The  machine 
number is 25, 25=1+8+16, just need to turn 1,4,5 to ON. 
2) Initializing Operation: Turn the dail 10 to ON, then turn it to OFF 
after 500ms. 
3)Function for the intercom linkage (installed with front door and 
back  door  in  the  elevator  car):It  should  be  worked  with  group 
controller.The default setting is OFF 
JP1 And JP2Fire Signal Type Setting
 
JP1 is used to specify that the input signal type of the fire signal 
terminal(XF+,XF-) is voltage signal or the switching value signal 
(including dry contact and open collector electronic switch )   
JP2 is used to specify that the state of the input signal is normal 
and effective. The logical constructions are as follows:   
Chart 2-1-3 Description of fire signal type setting 
JP1 
JP2 
Description 
Short Circuit 
Short  circuit 
3-2 
XF+、
XF- inputs short-circuit signal,
the system 
will enter the fire mode 
Short Circuit 
short circuit 
1-2 
XF+、XF- inputs open-circuit signal,the system 
will enter the fire mode