Shenzhen ITLONG Intelligent Technology CO. LTD HLD-DT-A Manuel D’Utilisation
13
Cut Off
short circuit
3-2
XF+、XF- inputs 0~7V voltage, the system will
enter the fire mode
Cut Off
short circuit
1-2
XF+、
XF- inputs 8~24V voltage, the system will
enter the fire mode
Note: When the fire terminal on the controller received the fire
signal, the system will enter the fire mode. Under the fire
mode,the elevator will recover to the original state (without the
access control system).
Default setting: JP1short circuit、JP2 short circuit 3-2 。
Optional Jumper: JP6
—Floor signal collector communication
terminal resistance
When the controller connect with the floor signal collector in
RS-485 communication mode, the jumper should be connected if
the controller is attached to the end of the communication cable.
Optional Jumper: JP7
—Computer communication terminal
resistance
When the controller connect network with the computer in RS-485
communication mode, the jumper should be connected if the
controller is attached to the end of the communication cable.
2.2 Expansion Relay Interface Instruction
The main board of the controller can controls 16 floors, if beyond
16 floors, the expansion relay board would be needed. One
expansion relay board can control 8 floors , support max quantity
of the expansion relay board is 12pcs, that is, 112 floors can be
controlled.
One or two expansion relay boards are installed in the expander,
the expansion relay board will be set the machine number
according to its functions and controlled floors.