13 
 
Cut Off 
short circuit 
3-2 
XF+、XF- inputs 0~7V voltage, the system will 
enter the fire mode 
Cut Off 
short circuit 
1-2 
XF+、
XF- inputs 8~24V voltage, the system will 
enter the fire mode 
Note:  When  the  fire  terminal  on  the  controller  received  the  fire 
signal,  the  system  will  enter  the  fire  mode.  Under  the  fire 
mode,the  elevator  will  recover  to  the  original  state  (without  the 
access control system).   
Default setting: JP1short circuitJP2 short circuit 3-2   
Optional Jumper: JP6
—Floor signal collector communication 
terminal resistance 
When  the  controller  connect  with  the  floor  signal  collector  in 
RS-485 communication mode, the jumper should be connected if 
the controller is attached to the end of the communication cable.   
Optional  Jumper:  JP7
—Computer  communication  terminal 
resistance 
When the controller connect network with the computer in RS-485 
communication  mode,  the  jumper  should  be  connected  if  the 
controller is attached to the end of the communication cable.   
2.2 Expansion Relay Interface Instruction   
The main board of the controller can controls 16 floors, if beyond 
16  floors,  the  expansion  relay  board  would  be  needed.  One 
expansion relay board can control 8 floors , support max quantity 
of the expansion relay board is 12pcs, that is, 112 floors can be 
controlled. 
One or two expansion relay boards are installed in the expander, 
the  expansion  relay  board  will  be  set  the  machine  number 
according to its functions and controlled floors.