Panasonic CU-2E15GBE Manuel D’Utilisation

Page de 77
57 
15.2.1.5 
Error Code Table 
Diagnosis 
Display 
Abnormality / Protection control 
Abnormality 
Judgment 
Emergency 
operation 
Primary location to verify 
Note 
H11 
Indoor/Outdoor abnormal 
communication 
> 1 min after starting 
operation 
Indoor fan 
operation only 
(single type only) 
• Internal/external cable connections 
• Indoor/outdoor PCB 
 
H12 
Indoor unit capacity unmatched 
•  Indoor unit total capacity 
Multi only
H14 
Intake air temperature unmatched 
•  Intake air temperature sensor 
(defective or disconnected) 
 
H16 Outdoor 
Current 
Transformer 
•  Decreased amount of refrigerant 
• Outdoor PCB 
 
H19 
Indoor fan motor mechanism lock 
• Fan motor 
• Indoor PCB 
 
H23 
Indoor heat exchanger temperature 
sensor 
Continue for 5 sec 
•  Heat exchanger temperature sensor 
(defective or disconnected) 
 
H27 
Outdoor air temperature sensor 
Continue for 5 sec 
○ 
(Single type only) 
•  Outdoor air temperature sensor 
(defective or disconnected) 
 
H28 
Outdoor heat exchanger temperature 
sensor 1 
Continue for 5 sec 
○ 
(Single type only) 
•  Outdoor heat exchanger temperature 
sensor (defective or disconnected) 
 
H30 
Outdoor discharge pipe temperature 
sensor 
Continue for 5 sec 
•  Outdoor discharge pipe temperature 
sensor (defective or disconnected) 
 
H32 
Outdoor heat exchanger temperature 
sensor 2 (discharge pipe temp) 
Continue for 5 sec 
•  Outdoor heat exchanger temperature 
sensor (defective or disconnected) 
Multi only
H34 
Outdoor heatsink temperature sensor 
at Control Board 
Continue for 2 sec 
•  Outdoor heatsink temperature sensor 
at control board (defective or 
disconnected) 
Multi only
H36 
Outdoor gas pipe temperature sensor 
Continue for 2 sec 
•  Outdoor gas pipe temperature sensor 
(defective or disconnected) 
Multi only
H37 
Outdoor liquid pipe temperature 
sensor 
Continue for 2 sec 
•  Outdoor liquid pipe temperature 
sensor (defective or disconnected) 
Multi only
H39 
Abnormal indoor operating unit or 
standby units 
- - 
•  Piping connection error 
•  Indoor/outdoor connection cable 
connection error 
Multi only
H41 
Abnormal wiring or piping connection 
•  Wiring or piping connection 
CU-
2E15GBE
H97 
Outdoor fan motor mechanism lock 
•  Outdoor Fan Motor 
 
H98 
Indoor high pressure protection 
•  Air filter dirty 
•  Air circulation short circuit 
 
H99 
Indoor heat exchanger freeze 
prevention 
- - 
• Insufficient refrigerant 
•  Air filter dirty 
 
F11 
Cooling/heating cycle changeover 
abnormality 
4 times occurrences 
within 30 minutes 
• 4-way valve 
• V-coil 
 
F17 
Indoor standby unit freezing 
•  Outdoor expansion valve leakage 
•  Indoor unit pipe temperature sensor 
 
F90 
PFC circuit protection 
• Outdoor PCB 
•  Outdoor fan motor 
 
F91 
Refrigerant cycle abnormality 
2 times occurrences 
within 20 minutes 
•  No refrigerant (3-way valve is closed)
 
F93 
Outdoor compressor abnormal 
revolution 
4 times occurrences 
within 20 minutes 
• Compressor 
 
F95 
Cooling high pressure protection 
4 times occurrences 
within 20 minutes 
•  Outdoor refrigerant cycle 
 
F96 
IPM (power transistor) overheating 
protection 
- - 
• Express refrigerant 
•  Improper heat radiation 
• Outdoor PCB 
 
F97 
Outdoor compressor overheating 
protection 
4 times occurrences 
within 10 minutes 
• Insufficient refrigerant 
• Compressor 
 
F98 
Total running current protection 
3 times occurrences 
within 20 minutes 
• Excess refrigerant 
•  Improper heat radiation 
 
F99 
Outdoor Direct Current (DC) peak 
detection 
7 times occurrences 
• Outdoor PCB 
• Compressor 
 
 
Note: 
“○” – Frequency measured and fan speed fixed.