Superior Essex 09-097-02 Manuel D’Utilisation

Page de 250
B-11
Toll Free 800.551.8948 | Fax 770.657.6807 | 
Rev 11/10  Ed 10.4
Dry Block/Sunlight Resistant Indoor/Outdoor 
OFNR
Specifications
2-12 Fiber 
Single Unit Design 
Configuration
Flexible tight buffer material extruded over fiber to 900 μm 
diameter; color coded fibers are combined with dielectic 
aramid yarns for strength and water blocking
18-36 Fiber 
Multi-Unit Design 
Configuration
Dry water-blocked 6-fiber sub-units are grouped to form cable 
core; core consits of sub-units cabled with additional 
strength members and water blocking elements
48-144 Fiber 
Multi-Unit Design 
Configuration
Dry water-blocked 12-fiber sub-units are grouped to form 
cable core; core consists of sub-units cabled with 
additional strength members and water blocking elements
Jacket
Black, flame retardant, chemical and sunlight resistant PVC
Performance 
Compliance
UL 1651
CSA C22.2 No. 232
UL 1666
Telcordia gR-20-CORE, Issue 3
ANSI/ICEA S-104-696-2001
ANSI/TIA-568-C.3
RoHS-compliant
NRTL Programs
UL, c(UL) Listed OFNR
UL, c(UL) Listed Sunlight Resistant
Environmental Specifications
Operation
-40°C to +75°C
Storage/Shipping
-40°C to +75°C
Installation
-20°C to +65°C
Part Numbers and Physical Characteristics
Part Number¹
Fiber Count
Nominal 
Diameter
in (mm)
Nominal Weight
lbs/kft (kg/km)
Maximum Tensile Loading
Minimum Bend Radius
Install
lbs (N)
Long Term
lbs (N)
Install
in (mm)
Long Term
in (mm)
W3002xx01
2
0.20 (5.0)
14 (21)
300 (1,340)
90 (400)
3.0 (75)
2.0 (50)
W3004xx01
4
0.20 (5.0)
15 (23)
300 (1,340)
90 (400)
3.0 (75)
2.0 (50)
W3006xx01
6
0.20 (5.0)
16 (23)
300 (1,340)
90 (400)
3.0 (75)
2.0 (50)
W3008xx01
8
0.24 (6.0)
21 (31)
300 (1,340)
90 (400)
3.5 (90)
2.4 (60)
W3012xx01
12
0.26 (6.5)
25 (38)
300 (1,340)
90 (400)
3.8 (97)
2.6 (65)
W3018xx01
18
0.55 (14.1)
100 (149)
600 (2,700)
180 (800)
8.3 (211)
5.5 (141)
W3024xx01
24
0.59 (14.9)
122 (182)
600 (2,700)
180 (800)
8.8 (224)
5.9 (149)
W3030xx01
30
0.63 (16.1)
147 (220)
600 (2,700)
180 (800)
9.5 (242)
6.3 (161)
W3036xx01
36
0.70 (17.7)
179 (267)
600 (2,700)
180 (800)
10.5 (266)
7.0 (177)
W3048xx01
48
0.70 (17.8)
161 (241)
600 (2,700)
180 (800)
10.5 (267)
7.0 (178)
W3060xx01
60
0.78 (19.8)
204 (304)
600 (2,700)
180 (800)
11.7 (297)
7.8 (198)
W3072xx01
72
0.84 (21.3)
243 (362)
600 (2,700)
180 (800)
12.6 (320)
8.4 (213)
W3084xx01
84
0.91 (23.2)
294 (439)
600 (2,700)
180 (800)
13.7 (347)
9.1 (232)
W3096xx01
96
0.98 (25.0)
345 (515)
600 (2,700)
180 (800)
14.8 (375)
9.8 (250)
W3144xx01
144
1.11 (28.3)
375 (559)
600 (2,700)
180 (800)
16.7 (425)
11.1 (283)
Single Mode Optical Fiber
Multimode Optical Fiber
Reduced 
Water Peak
Zero  
Water Peak
TeraFlex
®
 
Bend Resistant
Teragain
® 
62.5/125
Teragain Laser Optimized 50/125
TeraFlex Bend Resistant  
Laser Optimized 50/125
10g/150
10g/300
10g/550
10g/150
10g/300
10g/550
¹Replace “xx” with:
31
21
K1
¹Replace “xx” with:
6g
Ag
Bg
Fg
Mg
Ng
Pg
See the "Optical Fiber Selection Chart" in the "TECHNICAL INFO" section for detailed fiber type specifications.
Product Description
The Dry Block, Sunlight Resistant Indoor/Outdoor Tight Buffer Riser Rated 
Cable line offers the system designer the ultimate in premises optical fiber 
cable utility. These cables can be installed in open spaces, trays, conduits, 
inner-ducts,  trenches,  steam  tunnels  and  building  riser  locations.  These 
cables incorporate the latest in dry water blocking technology. This system 
of water blocking eliminates the need to clean off the traditional gel-based 
water blocking compounds found in loose-tube cables. In addition, breakout 
kits and or other special termination equipment associated with loose tube 
Outside Plant (OSP) cables are not required. The outer jacket is comprised 
of a rugged UL Listed, sunlight resistant, black polymer that allows for the 
cable  to  be  exposed  to  long-term  direct  sunlight  without  the  concern  of 
material  degradation.  All  fiber  types  are  available,  including  50/125  μm, 
62.5/125 μm and single mode.
Applications
•  Intra/inter-building backbones
•  Trench/conduit/duct/tray pathways
•  Dry or wet locations
Features
Benefits
•  Exceeds ANSI/TIA-568-C.3  
optical performance
•  Future-proof fiber performance 
for current and future multi-
gigabit applications
•  Dry-block design meets  
Telcordia gR-20-CORE water 
block requirements
•  Cable integrity maintained  
even if damage occurs to 
protective layers
•  900 μm tight-buffered fibers
•  Attaches directly  
to mechanical connectors
•  UL/NEC Listed OFNR
•  Eliminates the need to purchase 
separate cables for OSP and 
indoor/riser applications
•  All dielectric
•  No additional grounding materials 
need to be purchased
•  Jacket rip cord
•  Saves time in cable preparation
•  Black, UL Listed sunlight  
resistant outer jacket
•  Long periods of direct sunlight 
exposure will not damage cable
Flame Retardant PVC Jacket
Flame Retardant, Chemical and
Sunlight Resistant PVC Jacket
Buffered Optical Fiber
Water Blocking Dielectric
Aramid Strength Members
Water Blocking Tape
Rip Cord
Central Strength Member