Enda EI7412-SM-AS12 SW Universal LED-display EI7412 0 - 20 mA/4 - 20 mA/0 - 1 V/0 - 10 V Assembly dimensions 68 x 68 mm EI7412-SM-AS12 SW Fiche De Données
Codes de produits
EI7412-SM-AS12 SW
A.HYS. = Alarm hysteresis value.
Can be adjusted between 1 and 200.
See NOTE 1 for programming.
Can be adjusted between 1 and 200.
See NOTE 1 for programming.
A.tyP. = Function of alarm output.
Three kinds of functions can be selected.
IndE = Independent.
De = Deviation.
band = Band.
See NOTE 1 for programming.
Three kinds of functions can be selected.
IndE = Independent.
De = Deviation.
band = Band.
See NOTE 1 for programming.
Alr.
A.typ.
a.HYS.
a.sta.
A.UP.L.
A.Lo.L.
o.HYS. = Out hysteresis value.
Can be adjusted between 1 and 200.
See NOTE 1 for programming.
Can be adjusted between 1 and 200.
See NOTE 1 for programming.
o.StA. = State of out.
If H1 is selected then out output is
energized above the out setpoint .
If Lo is selected then out output is
energized below the out setpoint .
See NOTE 1 for programming.
If H1 is selected then out output is
energized above the out setpoint .
If Lo is selected then out output is
energized below the out setpoint .
See NOTE 1 for programming.
o.UP.L = Out value upper limit.
Can be adjusted between out value
lower limit (o.lo.l.) and upper limit
for scale (H.SCL.).
See NOTE1 for programming.
Can be adjusted between out value
lower limit (o.lo.l.) and upper limit
for scale (H.SCL.).
See NOTE1 for programming.
o.lo.L. = Out value lower limit.
Can be adjusted between lower
limit for scale (L.SCL.) and out
value upper limit (o.UP.l.)
See NOTE1 for programming.
Can be adjusted between lower
limit for scale (L.SCL.) and out
value upper limit (o.UP.l.)
See NOTE1 for programming.
ASET
ASET
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
A.Sta. = State of alarm output.
If independent or deviation alarm is
selected the alarm output can be Lo
and HI. For Lo, alarm output is
energized below the alarm setpoint.
For HI, alarm output is energized
above the alarm setpoint. If band alarm
is selected this parameter can be
bI.HI and bo.HI. For bI.HI, alarm
output is energized between the band.
For bo.HI, alarm output is energized
out of the band.
See NOTE1 for programming.
If independent or deviation alarm is
selected the alarm output can be Lo
and HI. For Lo, alarm output is
energized below the alarm setpoint.
For HI, alarm output is energized
above the alarm setpoint. If band alarm
is selected this parameter can be
bI.HI and bo.HI. For bI.HI, alarm
output is energized between the band.
For bo.HI, alarm output is energized
out of the band.
See NOTE1 for programming.
Run mode
Measured
value
value
d.Cnf.
i.typ.
rate
Hold
dsp.C.
Unit
SET
OSET
ASET
&
SET
OSET
ASET
ASET
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
a.UP.L. = Alarm value upper limit.
Can be adjusted between higher limit
for scale (H.SCL.) and alarm value lower
limit (a.Lo.L.).
See NOTE1 for programming.
Can be adjusted between higher limit
for scale (H.SCL.) and alarm value lower
limit (a.Lo.L.).
See NOTE1 for programming.
a.Lo.L. = Alarm value lower limit.
Can be adjusted between lower limit for
scale (L.SCL.) and alarm value upper
limit (a.UP.L.).
Can be adjusted between lower limit for
scale (L.SCL.) and alarm value upper
limit (a.UP.L.).
out.
o.Hys.
o.UP.L.
o.lo.L.
o.StA.
MIN
MAX
MIN
MAX
MIN
MAX
MIN
Page 3/4
Programming mode
Page 3/4
1000
Out set value
SET
OSET
500
MAX
MIN
SET
OSET
499
SET
OSET
500
Out set value
Out set value
SET
OSET
MAX
MIN
NOTE 1
MAX
Parameter adjustment method
SET
OSET
1000
MAX
MIN
SET
OSET
999
SET
OSET
1000
L.SCL.
SET
OSET
While holding key out set value flashes and by using keys the value can be adjusted.
Out set value changes fastly if increase or decrease key is pressed for 0.6 second.
SET
OSET
MAX
MIN
While holding key out set value flashes and by using keys the value can be adjusted.
If increment key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly.
If waited enough, the value increases 100 at each step. After 1 second following the release of the key, initial
condition is returned. The same procedure is valid for the decrement key.
condition is returned. The same procedure is valid for the decrement key.
i.typ. = Input type.
Input type can be selected as 0-20mA,
4-20mA, 0-1V or 0-10V.
See NOTE 1 for programming.
Input type can be selected as 0-20mA,
4-20mA, 0-1V or 0-10V.
See NOTE 1 for programming.
dSP.C. = Display configuration.
Selectable as PrcS. or Pr.Un. . If PrcS. is
selected, process value appears. If Pr.Un. is
selected, process value and then
measurement unit are displayed 4 and 2
seconds successively.
See NOTE 1 for programming.
Selectable as PrcS. or Pr.Un. . If PrcS. is
selected, process value appears. If Pr.Un. is
selected, process value and then
measurement unit are displayed 4 and 2
seconds successively.
See NOTE 1 for programming.
RAtE = Sampling rate.
Measurement is performed at each 200ms.
However,
for FASt rate, each measurement is displayed.
for SLo.1 rate, the average of 4 successive
measurements is displayed.
for SLo.2 rate, the average of 8 successive
measurements is displayed.
for SLo.3 rate, the average of 16 successive
measurements is displayed.
See NOTE 1 for programming.
Measurement is performed at each 200ms.
However,
for FASt rate, each measurement is displayed.
for SLo.1 rate, the average of 4 successive
measurements is displayed.
for SLo.2 rate, the average of 8 successive
measurements is displayed.
for SLo.3 rate, the average of 16 successive
measurements is displayed.
See NOTE 1 for programming.
Hold = Display holding parameter.
Selecting NonE , this parameter becomes
inactive.
Selecting Lo. , always the minimum measured
value is displayed.
Selecting Hi. , always the maximum
measured value is displayed.
Selecting NonE , this parameter becomes
inactive.
Selecting Lo. , always the minimum measured
value is displayed.
Selecting Hi. , always the maximum
measured value is displayed.
For including decimal point first, then,
keys are pressed and held together. And
then, by using key decimal point can be
adjusted.
adjusted.
SET
OSET
MAX
MIN
Unit = Measurement unit.
A constant, a message etc. to be displayed can
be entered. If a decimal point is desired, it
should be included before entering the
character.
A constant, a message etc. to be displayed can
be entered. If a decimal point is desired, it
should be included before entering the
character.
The message on the left flashes approximately 5
seconds and calibration is completed.
seconds and calibration is completed.
The message on the left flashes approximately 5
seconds and calibration is completed.
seconds and calibration is completed.
If calibration is error free, the message
C.End
appears for 1 seconds. However,
if it is wrong, the message
S.Err
.
appears for 1 seconds and the program
is shifted to the next step.
is shifted to the next step.
If calibration is error free, the message
C.End
appears for 1 seconds. However,
if it is wrong, the message
C.Err.
appears for 1 seconds and the program
is shifted to the next step.
is shifted to the next step.
If the difference between the reference voltages or currents applied for the calibration of
H.inP.
and
L.inP.
is lower than one
half of the full scale, this error message appears on the display.
For example: Assume that the selected input type is 0-1V. In this case, if the difference between the reference voltages
applied for calibration of
For example: Assume that the selected input type is 0-1V. In this case, if the difference between the reference voltages
applied for calibration of
H.inP.
and
L.inP.
is lower than 0.5V, this error message appears.
If the reference voltage or current applied to the input for calibration is too high or too low, this error message appears.
ERROR MESSAGES
Yes
No
NOTE 2
CAL.
CAL okey?
C.end
s.err.
C.err.
s.err.
NOTE 3
CAL.
Yes
No
CAL okey?
C.end
C.err.
SET
OSET
ASET
If first and then keys are pressed together programming mode is entered
2./4 EI7412-E