IMPORTANT NOTE:
The “PARITY” should be selected as 
None
 in order to communicate with MPR-SW Software.
4.5  Datalog
Prt (Parity Settings)
Parity settings are set as none, even or odd.
Parameter Settings
Figure 20: 
Setting the “Pr12” Parameter
Per (Period Menu)
Period is the time interval between 2 consecutive records and can be set between 5 - 32.000 seconds.
If period is set to “off”, then no parameters will be recorded.
Figure 19: 
Setting the Parity Settings
Figure 21: 
Setting the period time
Warning :
You may quit all settings any time by           key.
You must record any change in the settings by         menu key.
Device records the choosen 28 parameters in its 
1 MB memory
 with date and time stamp. The choice of the
parameters and recording details are set in Datalog menu. These records can be monitored on the PC and
not affected by energy cut off.
The “Datalog” menu has 30 sub-menus.
“Pr1:...” “Pr2:...” .......     “Pr28:...”  ,  “Per:..”. ,  “Event:...”
“Pr1: ...” “Pr2: ...”   ........  “Pr28:...” (Parameter Menus)
28 parameters can be associated with these sub menus with one parameter per each menu which will be
recorded to memory
The parameters that can be see in parameter tables (See page 43).
15.000 record lines can be stored in memory on the condition, where the total 28 parameters are called as
one record line.
At 15.001st record, the first 1000 records are cleared automatically. And then, last record will be read as
14001th.
Note:
Even if less than 28 parameters are entered in sub menus, devices memory allocation is still
for 28 parameters for each record line. So assigning  less parameters do not increase memory 
capacity.