Entes MPR-63 Mains-analysis device, Mains analyser MPR-63 Manuel D’Utilisation

Codes de produits
MPR-63
Page de 47
In device
,
this feature gives the possiblity that observing the measured values by
other devices with converting these values in to 0-10 V or 2-10 V voltage data.
The below parameters can be set as analog output in device
.
43
4.21 Voltage Analog Output (0/2-10V) 
(Only for MPR63
-22/23
)
The below parameters can be set as analog output 
:
L
L
L
N
V
L1, L2, L3 
(V)
(Phase Voltage)
V
L12, L23, L31 
(V)
(Phase-Phase Voltage)
V.
    (Average)
(Average of the total phase voltages)
V.
    (Average)
(Average of the total phase-phase voltages)
Frequency 
(Hz)
(Frequency)
I
L1, L2, L3 
(A)
(Phase Currents)
THD %V
L1, L2, L3 (Total Harmonic Values for Voltages)
THD %I 
L1, L2, L3  (Total Harmonic Values for Currents)
P
L1, L2, L3 
(W)
(Active Power)
Q
L1, L2, L3 
(VAr)
(Reactive Power)
S
L1, L2, L3 
(VA)
(Apparent Power)
I. 
(A)
(Total Phase Currents)
P. 
(W)
(Total Active Power)
Q. 
(VAr)
(Total Reactive Power)
S. 
(VA)
(Total Apparent Power)
MPR63
-23
For example
Below settings should be fulfilled as like :
Type
: 2-10 V
Prm (Parameter)  : I
L1
Lo(Low value)  
: 100 mA
Hi (High value)
: 5 A
After above settings are completed;
Analog voltage output’s value will be 2 V when I
L1
 value is 100mA,
Analog voltage output’s value will be 10 V when I
L1
 value is 5 A.
When I
L1
 is 3.5 A analog voltage output value will be;
I
out
= (10-2)x(3.5-0)
(5-0.1)
+ 2 = 7.714 V
(10-0)x[400-(-250)]
[750-(-250)]
= 6,5 V
For example
Below settings should be fulfilled as like :
Type
: 0-10 V
Prm (Parameter)  : 
Σ
Q
Lo(Low value)  
: -250 VAr
Hi (High value)
: 750 VAr
After above settings are completed;
Analog voltage output’s value will be 0 V when 
Σ
Q value is -250 VAr,
Analog voltage output’s value will be 10 V when 
Σ
Q value is 750 VAr.
When
Σ
Q is 400 VAr analog voltage output value will be;
I
out
=
L1
L2
L3
1
2
3
4
5
6
17
18
19
20
26
25
7
L1
8
L2
9
L3
10
N
L1
L2
L3
k
l
K
L
k
l
K
L
k
l
K
L
1. Relay 1
2. Relay 2
21 22 23 24
3. Input 1
Max:30VDC
+
_
4. Input 2
RS-485
11 12 13
GND
14
A
15
B
16
TR
Analog
Out-1
External
Supply
Voltage Measurement Inputs
Current Measurement Inputs
Ýnput 1
Ýnput 2
27 28
Analog
Out-2
RS-485
11 12 13
GND
14
A
15
B
16
TR
Analog
Out
27 28
Analog
Out-2
3 phase without neutral connection
A
L1
N