Clamp Current Test (
) (GT-800 only) 
 
The test with the external clamp adapter measures the current in clamped 
conductor. The function is intended to measure: 
 
  The protective conductor current (earth leakage current) in the protective 
conductor (PE). 
  The load current in line (or neutral) conductor. 
 
Remarks: 
  Connect the clamp according to the figure 23, 24 or 25. 
  Select appropriate measurement range by using soft menu key “RNG” (F1)   
(0 ... 20 mA for leakage current or 0 ... 60 A for load current). 
 
 
 
Figure 23: Protective conductor current test connection (differential method) 
 
 
 
 
Figure 24: Protective conductor current test connection (direct method)