AUTO-TEST Menu
In this menu the following selections are available:
MODIFY / VIEW:
MODIFY / VIEW:
Modify/view (customer-created AUTO Tests) or just view
(factory-programmed AUTO Tests).
(factory-programmed AUTO Tests).
Select the AUTO Test you wish to modify/view first by
using the “A
using the “A
▼” and “A▲” menu keys then confirm the
MODIFY/VIEW selection by pressing the “
” menu key.
Now use the “
▼”, “▲” menu keys to select the desired
AUTO Test step.
At customer-created AUTO Tests two menu keys “EDIT”
and “PAR” appear which allow the modification of the
selected AUTO Test step. “EDIT” key enables to remove
or add test step, “PAR” key enables to modify limit value
or test parameter (e.g. test voltage in R
and “PAR” appear which allow the modification of the
selected AUTO Test step. “EDIT” key enables to remove
or add test step, “PAR” key enables to modify limit value
or test parameter (e.g. test voltage in R
ISO
function).
RENAME AUTO-TEST:
Select the AUTO Test you wish to rename first by using
the “A
the “A
▼” and “A▲” keys then confirm the RENAME
AUTO Test selection by pressing the “
” key. Use the
“
▼”, “▲” and “
” menu keys to create new name,
then confirm the new name by pressing the “
” key.
CREATE AUTO-TEST:
Create new AUTO Test as follows:
-
-
Create the name of the new AUTO Test by using the
“
▼”, “▲” and “
” menu keys then confirm the
name by pressing the “
” key.
-
Select protection class of the new AUTO Test (PC I or
PC II) then confirm it by pressing the “
” key.
-
Select the tests to be contained in the new AUTO Test
by using the rotary switch and confirm each individual
test by the “
test by the “
” key. End the selection by pressing the
“END” key, the display turns to EDIT/ADJ mode.
Notes for setup of new AUTO Test!
Test current in R
PE
test (5 A or 0.2 A) and test voltage in R
ISO
test (500 V (HI)
or 250 V (LO)) can be selected by using the menu keys “Im” and “U
ISO
”
during setup of new AUTO Test.
Measurement range in CLAMP test (0 ... 60 A (HI) or 0 ... 20 mA (LO)) can be
selected by using the menu key “RNG” during setup of new AUTO Test.
Limit value in R
PE
test is always copied from individual R
PE
test.
Limit value in P/I
L
test is always set to 3.7 kVA.
There is no limit value available in CLAMP test.
Limit value in all other tests is always set to standard value.
Edit (add/remove some tests) the AUTO Test by using the “EDIT” menu key
Limit value in all other tests is always set to standard value.
Edit (add/remove some tests) the AUTO Test by using the “EDIT” menu key
or adjust limit values and/or test parameters by using the “PAR” menu key.
COPY AUTO-TEST:
Select the AUTO Test you wish to copy first by using the
“A
▼” and “A▲” menu keys then confirm the COPPY
AUTO-TEST selection by pressing the “
” menu key.
Confirm/abort offered selection by pressing the “YES” /
”NO” menu key.