• For the heating insulation lay out the insulation boards on the rough floor surface which
must be cleaned before from dirt and dust.
• Cut a recess in the rough floor surface or in the insulation board for the floor sensor. The
floor sensor should be located underneath the heating element and between two heating
cables and at least 10 cm away from the wall. It is recommended to insert the floor sensor
in an empty pipe (see figure 3). This allows, if necessary, to replace the floor sensor,
without opening the ground floor.
cables and at least 10 cm away from the wall. It is recommended to insert the floor sensor
in an empty pipe (see figure 3). This allows, if necessary, to replace the floor sensor,
without opening the ground floor.
•
Lay out the heating elements according to your lay out plan. The heating elements will be
placed on the heating insulation with the adhesive side down. Cut the glass fibre webbing
accurately without causing damage to the heating cable (see figure 4).
accurately without causing damage to the heating cable (see figure 4).
Figure 4
During the lay out of the heating element assure oneself that the floor sensor is
located between two meanders of the heating cable. The floor sensor must not get in
contact or cross the heating cable (see figure 5).
located between two meanders of the heating cable. The floor sensor must not get in
contact or cross the heating cable (see figure 5).
Figure 5
It is strictly forbidden to shorten the heating element or the heating cable.
• Lay the connection cables (cold conductors) to the connection point (thermostat). Disallow
that the connection cables cross with each other or with the heating cable. It is allowed, if
necessary, to shorten or to extend the connection cables (cold conductors).
necessary, to shorten or to extend the connection cables (cold conductors).
• Measure the resistance of the heating element and record the value on the guarantee card.
Assure oneself that the measured value of the resistance is conform to the recorded value
on the guarantee card.
on the guarantee card.
• Install all the necessary electrical utilities. By the use of two or more heating elements
connect the cold conductor in a parallel circuit.
• Switch on the electrical floor heating elements for a certain time and assure oneself that all
the heating elements operate properly.
• Lay the laminate floor. At the same time use soft footwear in order to avoid that the heating
cable gets damaged.
Use for heat insulation soft materials – a soft impact sound insulation or an insulation with
good heat insulation characteristics and a minimum thickness of 3 mm - which is specified for
laminate and wooden floor. To receive the best heating results, the whole floor construction
combined (generally insulation and laminate) should not exceed the thermal resistance of
0,15 m
2
K/W.