Bender IR420-D4-2 B71016405 Fiche De Données
Codes de produits
B71016405
TDB101012en / Main catalogue part 1 – Insulation monitoring / 09.2011
33
1.1
A-ISOMETER® IR420
Operating elements
Wiring diagram
1 -
LED Power "ON", flashes in case of interruption of the connecting
leads earth/ KE or L1 / L2.
2 -
Alarm LED "AL1", lights when the value falls below the set response
value Alarm 1 and flashes in case of interruption of the connecting
leads earth/KE or L1/L2).
leads earth/KE or L1/L2).
3 -
Alarm LED "AL2", lights when the value falls below the set response
value Alarm 2 and flashes in case of interruption of the connecting
leads earth/KE or L1/L2).
leads earth/KE or L1/L2).
4 -
LC display
5 -
Test button "T": to call up the self test.
Arrow up button: Parameter change, to move up in the menu.
6 -
Reset button "R": to delete stored insulation fault alarms
Abwärts-Taste: Parameter change, to move down in the menu.
7 -
"MENU" button: to call up the menu system.
Enter button: to confirm parameter change
1 -
Supply voltage U
S
(see ordering information) via fuse
2 -
Separate connection of E and KE to PE
3 -
Connection to the AC system to be monitored:
AC: connect terminals L1, L2 to conductor L1, L2.
4 -
Alarm relay K1: Alarm 1
5 -
Alarm relay K2: Alarm 2
6 -
Combined test and reset button "T/R"
short-time pressing (< 1.5 s) = RESET
long-time pressing (> 1.5 s) = TEST
long-time pressing (> 1.5 s) = TEST
7 -
Line protection by a fuse in accordance with IEC 60364-4-43
(6 A fuse recommended). In case of supply (A1/A2) from an
IT system, both lines have to be protected by a fuse.
IT system, both lines have to be protected by a fuse.
1
1
2
7
4
5
3
6
2
3
4
5
6
7