Periodic maintenance  62 
Component to be inspected 
Task 
Frequency 
Capable Party 
Condensate drain lines and 
p-trap 
Inspect and verify that: 
 
There is no internal blockage 
of the drain line 
 
Condensate can freely pass 
 
P-traps are intact and not 
leaking 
 
There is no blockage of the 
drain line that is external to the 
site drain 
Clean and clear debris as 
necessary. 
Quarterly 
Qualified personnel 
Heat exchanger fans 
Inspect and verify that the 
following components are 
properly secured and operational: 
 
Fan 
 
Fan mounting  
 
Wiring harness 
 
Power modules (located in the 
ECS cabinet) 
Quarterly 
Qualified personnel 
Chilled water header drain pan 
and lines 
Visually check drains for internal 
and external blockage 
 
Monthly, if 
staffed 
 
Quarterly, if 
not staffed 
Qualified personnel 
— 
Conduct an operational check of 
the external site drain using 
approximately 5 gallons of water 
(if possible) 
Annual 
Qualified personnel 
 
 
Leak detection 
The HP POD 20c includes six heat exchanger condensate sensors. Three sensors are located in the drain 
pans below each set of heat exchangers, and three sensors are located in the chilled water supply and return 
header drain pan tray. 
Some amount of condensation water can always be expected in the heat exchanger drain pans. If an 
excessive amount of condensation water accumulates in a drain pan, an alarm is triggered and sent through 
the HP POD 20c ECS, which indicates a possible leak. 
There should be no water in the chilled water supply and return header drain pan. The drain pan should 
always remain dry. 
 
Leak isolation 
  
 
WARNING:
  To reduce the risk of electric shock or damage to the equipment, use extreme 
caution when removing and replacing components that involve water around the electrical 
equipment. There is great risk of electrical shock when water is used near electricity.