HP Performance Optimized Data Center (POD) 20cp Guide De Montage

Page de 22
 
Water quality requirements  16 
Piping materials 
Do not use the following interconnecting piping materials in a closed water system: 
• 
Oxidizing biocides 
• 
Aluminum components 
• 
Brass components with high levels of zinc 
• 
Non-stainless steel iron components 
 
Water precautions 
Take the following precautions before installation of the HP POD: 
• 
Verify that all foreign matter and particulates are flushed from the system. Water might be discolored 
during the initial flushing of the system. Clear running water is the sign that all foreign matter and 
particulates have been flushed from the system. 
• 
Evaluate the short-term and long-term system requirements against the available water capacity. 
• 
Ensure that the chilled water loop is properly designed for liquid cooling systems and is separate 
from the sanitary water systems in your building (bathroom, sink, drinking water). 
• 
Ensure facility managers are aware of the additional load being added to the chilled water supply of 
the building. Be aware that the added heat load might affect other components being cooled by the 
chilled water plant. 
 
Condensation management 
  
 
CAUTION: 
 During operation, avoid leaving the HP POD doors open, to maintain accurate 
environmental conditions inside the HP POD. 
  
Supply cooling water that is above the dew point inside the HP POD to prevent condensation forming on 
the heat exchangers. 
The heat exchanger drip tray will collect any condensation that forms on the heat exchangers. This 
collected condensate drains out of the HP POD through the heat exchanger condensate drains. HP 
recommends connecting condensate drains on the HP POD to a facility drain to prevent collection of 
water near the HP POD. 
There is one heat exchanger condensate drain outlet located near the bottom of the HP POD in between 
the access doors on the hot aisle side. There are three drains for the water main supply and return lines 
located near the bottom of the HP POD on the cold aisle side. 
To avoid excessive buildup of condensate and to conserve energy, raise the cooling water temperature to 
above the dew point to manage condensation while maintaining the necessary cooling capacity.