HP Performance Optimized Data Center (POD) 20cp Guide De Montage

Page de 22
 
Power management  17 
Power management 
Connection requirements 
When determining the final location of your power and water connections, consider the distance between 
the facility utilities and the HP POD. 
The facility power connection must be installed in compliance with local electrical codes and regulations. 
HP can provide engineering services to develop the site installation plan and drawings as a supplemental 
service. 
 
Power requirements 
The HP POD is available in North American and International models. Both models provide 145 kW 
redundant or 290 kW non redundant power for the critical load. 
• 
The North American HP POD includes step-down isolation transformers and requires two 400A, 
480V, 3-phase delta feeds at 50-60 Hz. 
• 
The International HP POD does not require transformers and requires two 400A, 380-415V, 3-phase 
wye feeds at 50-60 Hz. All 3-phase HP POD feeders require that the neutrals and the equipment 
grounding conductors remain isolated. Bonding of the two conductors is allowed at the power 
source only. 
For higher density loads that require more power capacity, both 400A inputs can be fed from the same 
source. When a lower density critical load is used, N+N redundancy can be accomplished by connecting 
the two 400A feeds to independent sources. 
 