Eaton Electrical Wireless Office Headset SC200 Manuel D’Utilisation

Page de 78
Control Function Glossary 
B-2 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
 
 
Low Volts Disconnect 
Low Voltage Disconnect disconnects the batteries (Battery Disconnect) or the load (Load 
Disconnect), at the preset LVD disconnect voltage.  This prevents damage to the batteries 
due to excessive deep discharge.  The LVD reconnects the batteries or loads after the AC 
power is restored. 
 
 
When configuring the LVD reconnect voltage, ensure that the expected open-circuit recovery 
voltage of the discharged batteries does not rise above the LVD reconnect voltage. 
Temperature Compensation 
Temperature Compensation automatically varies the float voltage to cancel the effects of 
increasing or decreasing ambient battery temperature. 
As the ambient temperature of the batteries increases, the voltage required to maintain it in a 
fully charged state decreases. 
Enable Temperature Compensation to help maintain optimum battery capacity over a wider 
temperature range, which in turn extends battery life.