Eaton Electrical Wireless Office Headset SC200 Manuel D’Utilisation
Appendix
C
Specifications
Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.
IPN 997-00012-41D December 2006
C-1
System AC Input
AC Input Voltage Range
APU48 rectifiers: 95 – 275 V
rms
(L-N)
APR48 rectifiers: 185 – 275 V
rms
(L-N)
Rated AC Input Current
APS3: 21 A
(7 A per AC power cord)
@ 120 V
rms
with APU48 rectifiers
APS6: 42 A
(7 A per AC power cord)
APS3: 10.5 A
(3.5 A per AC power cord)
@ 240 V
rms
with APU48 rectifiers
APS6: 21 A
(3.5 A per AC power cord)
APS3: 24 A
(8 A per AC power cord)
@ 208-240 V
rms
with APR48 rectifiers
APS6: 48 A
(8 A per AC power cord)
Frequency Range
45-66 Hz
Maximum Earth Leakage Current
1.5 mA
(per Access Power Rectifier)
System DC Output
DC Output Voltage (nominal)
48 V
DC Output Power (maximum)
2.16
kW
(with 3 APU48 rectifiers)
APS3-058 & APS3-060
4.50 kW
(with 3 APR48 rectifiers)
1.70
kW
(with 3 APU48 rectifiers)
APS3-059 & APS3-061
3.00 kW
(with 3 APR48 rectifiers)
4.32
kW
(with 6 APU48 rectifiers)
APS6-058
9.00 kW
(with 6 APR48 rectifiers)
3.40
kW
(with 6 APU48 rectifiers)
APS6-059
7.10 kW
(with 6 APR48 rectifiers)
DC Output Voltage Range
43 - 57.5 V
Over Voltage Shutdown Trip Point
58 V
Environment
Ambient Temperature Range (operating)
-10°C to +40°C [+14°F to +104°F]
Relative
Humidity
(operating and storage)
<95% (non condensing)