Honeywell 805595 Manuel D’Utilisation

Page de 46
IQ8Wireless transponder for wall mounting 
 
40 
FB 798941 / 10.06 
11.1 Analog 
loop 
1. Connect the IQ8Wireless transponder to the analog loop of the IQ8Control fire alarm 
system and the external power supply as described in "Installation".  
2.  Switch on the fire alarm control panel or the analog loop to which the IQ8Wireless 
transponder is connected. If several IQ8Wireless transponders are connected, start these 
up one after the other to prevent multiple assignment of one wireless device. 
3.  Conduct a wiring recognition of the loop with the service PC and the tools 8000 
programming software. All devices on the analog loop are displayed. 
4.  Click the required IQ8Wireless transponder on this analog loop to open the dialog for 
programming the wireless transponder. 
5.  In the menu item “Measure signal strength” check if the quality of the wireless 
transmission between the transponder and the base is adequate.  
6.  All the wireless bases that this IQ8Wireless transponder has recognised are displayed in 
menu item "Assign wireless devices“. If several IQ8Wireless transponders exist, wireless 
bases that are already assigned to other IQ8Wireless transponders are not shown.  
7.  In the menu item “Assign wireless devices”, assign all required wireless bases to the 
IQ8Wireless transponder individually. The wireless devices can be assigned individually in  
individual detector zones. 
8.  Start-up is complete for this wireless transponder. Leave the IQ8Wireless transponder 
switched on and start up any other IQ8Wireless transponders that you have. 
 
805595
IQ8Control
IQ8Control
esserbus
®
-PLus
Service PC
Panel 
Interface
789862
 
Fig. 25: Commissioning 
Î
 Analog loop connection