Honeywell 805595 Manuel D’Utilisation

Page de 46
IQ8Wireless transponder for wall mounting 
 
38 
FB 798941 / 10.06 
10.6 Inputs 
-
+
Eing
-
+
U
B
Schnittstelle
1      2     3      4      5      6 
P
R
 
Fig. 23: Position of the terminals 
 
 
10.6.1 
R - input 
Input for connecting the transponder to a standard detector zone. This input is required for the 
reset function. If the transponder is connected to the analog loop of the IQ8Control fire alarm 
system, the input must not be connected. 
 
10.6.2 
P - terminal 
Free terminal point 
 
 
10.6.3 Interface 
(Schnittstelle) 
No function – do not connect terminals. 
This interface is for future feature extensions (e.g. direct connection of the service PC). 
 
 
10.6.4 Input 
(Eing) 
Reset input for an external RESET signal. The transponder is reset by applying voltage of 
9V DC to 30V DC for at least 1 second. 
 
 
10.6.5 U
B
 
Input for power supply 9 V DC to 30 V DC.