APPENDIX A – FAULT CODES 
 
CODE 
STATUS 
DESCRIPTION 
F01 
Over discharged battery (<1.90vpc after 30 seconds of charge) 
F02 
N 
Deep discharged battery (<1.90vpc after 30 seconds of charge > 1.90vpc) 
F03 
N 
Sulphated battery 
F04 
S 
Charger over heating 
F05 
Mains failed during charge 
F06 
R 
No output current 
F07 
C 
Incorrect battery < 1.70 
F07 (+Y led on) 
C 
Incorrect battery > 2.25 
F09 
C 
Bulk charge time-out 
F10 
C 
Second stage time-out (Profile Dependant) 
F11 
Incorrect Mains Frequency 
F12 
C 
Control hardware (MCU) 
F13 
S 
Thermistor fault 
F16 
S 
Battery overheating (if temp probe fitted) 
F17 
C 
Auto balance charge time-out 
F18 
C 
Battery disconnected without pausing charge 
F22 
C 
di/dt termination 
 
Key: - 
= critical fault 
Ö charge stopped Ö fault code displayed permanently 
= suspend fault 
Ö charge suspended until criteria fulfilled Ö fault code displayed permanently 
R  = retry fault 
Ö charge retries after 20 seconds Ö fault code display alternating with standard 
display 
= non-critical fault 
Ö charge continues Ö fault code display alternating with standard display