10.6 EQUALIZE 
PUSHBUTTON 
 
Equalize charge can be enabled/disabled, when the FUNCTION button is depressed 
> 5 second at anytime whilst a battery is connected. Only one equalize charge per 
recharge cycle is permitted.  
 
CAUTION:  DO NOT EQUALIZE MORE OFTEN THAN REQUIRED BY THE 
CONDITION OF THE BATTERY, AS SPECIFIED IN THE BATTERY 
MAINTENANCE INSTRUCTIONS. EXCESSIVE EQUALIZING MAY 
DAMAGE THE BATTERY. 
 
10.7  LOW BATTERY OVERRIDE/RECOVORY 
 
10.7.1 CONFIGURATION 
 
There is the ability to manually override the low ‘Incorrect Battery’ threshold 
of 1.70 VPC, down to a minimum of 1.00 VPC - the level at which the charger 
will recognize a battery connection. This is achieved by holding the 
FUNCTION push button for 5 seconds when the incorrect battery fault has 
been detected. 
 
10.7.2 OPERATION 
 
If ‘Low Battery Override’ has been enabled and a battery (voltage > 1.00 
VPC) is connected to the charger, the charger will pass current at 75% of the 
maximum output current. 
 
If less than 3.0VPC, current will flow for 5 minutes and the charge will be 
suspended for 5 minutes.  The cycle is repeated until the battery voltage is 
greater than 1.70 VPC at the end of the 5-minute rest period. 
 
If the battery voltage is greater than 1.70 VPC at the end of the 5-minute rest 
period, the battery recovery mode will cease and charge will start from stage 
1 with smart start disabled. 
 
If 3.0 VPC is reached within the 5 minutes of charge, the charge will be 
suspended equal to the ‘on’ time, maximum of 5 minutes. During this period 
the display will show ‘Lobt’.  During the 5-minute off period the display will 
show the battery volts per cell alternating with ‘Lobt’. 
 
10.8 
INCORRECT BATTERY LIMITS 
 
Incorrect battery detection limits will be < 1.70 VPC and > 2.25 VPC (off 
charge). If the battery voltage comes within this window the charger will 
automatically commence charging. 
 
10.9 
AC POWER FAILURE 
 
If the AC power fails during a charge cycle, the charger will resume the cycle 