Simrad AUTOPILOT SYSTEM AP50 Manuel D’Utilisation

Page de 188
 Installation 
20221032B
 85 
4.9  J50 Junction Unit 
The J50 Junction Unit is designed to operate in a location that 
provides ambient temperatures below +55°C (+130°F). 
Note ! 
The junction units (J50 and J50-40) are not waterproof and 
should be mounted vertically, as shown in Figure 4-11, in a dry 
place between the control unit and the drive unit. 
 
Figure 4-11  J50 Junction Unit Mounting 
Cable Connections 
Use only shielded cables. This includes Mains input, drive units, 
and, if necessary, for the extension of the RF300S Rudder 
Feedback Unit cable. The clutch/bypass cable and the solenoid 
cable should be 1.5 mm
2
 (AWG14). Signal cables should be 0.5 
mm
2
 (AWG20) twisted-pairs. 
The Mains supply cable and the drive unit motor cable should 
have sufficient wire gauge. This will minimize voltage drop and 
allow the drive unit to operate at full power. 
Refer to the table below for recommended cable sizes. 
Cable length 
Drive Unit Voltage 
1. Distribution Board to Junction Unit. 
12 V 
24 V 
2. Junction Unit to Drive Unit motor  
    (Length refers to each of the two cables) 
mm
2
 AWG  mm
2
 AWG 
Up to 3 m (10 ft.) 
2,5 
12 
2,5 
12 
Up to 6 m (20 ft.) 
10 
2,5 
10 
Up to 10 m (32 ft.) 
10 
Up to 16 m (52 ft.) 
10 
Table 4-1  Recommended Cable Sizes