2. Hints
  
 
2.9 Setting up a standard pressure application
 
Using a QBE sensor, 
Siemens part # QBE620-P10 [P10 is 150PSI] 
 
Configure 
 
 If no keys are pressed for 20 seconds, the controller will exit this 
mode, and return to the basic display. 
 
 See Hint section 2.2, ‘How to configuration your RWF40”.
 
(From the basic display, or user level, 
 press 
 
and hold, for 3 seconds,  
 
and then release, and again, 
 press  and hold, for 3 seconds,  
 
and then release) 
 
The actual value display, (
9030
shows the current configuration item value
 
The setpoint display, (
C111
shows the configuration item you are adjusting. 
 
The display is steady, (not flashing) and by default,  
the 4
th
, (rightmost) digit may now be adjusted. 
 
You can select which digit you wish to adjust, by  
pressing 
 once and releasing it. The 3
rd
 digit is now  
flashing, indicating that it is now, the adjustable digit. 
 
Cycle thru each digit of C111 and configure as charted 
below, then accept by pressing 
 and releasing.  
 
All four upper digits will flash once, and the new  
configuration value, is displayed in 4 steady digits. 
 
Press 
 and release, to configure C112, C113, … thru Df1. 
 
Configuration level values: 
 
Item  
Description 
Value 
* Sec 
 
C111   
G000 
 
 
Analog input 1 
Std Signal 0-1VDC 
8.1 
 
Analog input 2 
none 
8.1 
 
Analog input 3 
none 
8.1 
 
D2 function 
none 
8.1 
 
 
 
 
 
C112   
8200 
8.1 
 
Limit comparator 
input 1 
8.1 
 
Controller type 
modulating 4-20mA 
8.1 
 
Setpoint SP1 
via buttons 
8.2 
 
Locking 
none 
8.2 
 
 
 
 
 
C113   
0220 
 
 
Unit address 
02 
Modbus address  
8.2 
 
Decimal - Units 
(%) no decimals 
8.2 
 
Out-of-range Signal 
limit comparator OFF 
8.2 
 
 
 
 
 
SCL 
SCale Low 
Analog input 1 
8.3.1
 
SCH  SCale High 
150 
Analog input 1 
8.3.2
 
SCL2  SCale Low 
Analog input 2 
8.3.3
 
SCH2  SCale High 
100 
Analog input 2 
8.3.4 
SPL 
SetPoint Low  
150 
limits low setpoint to 160 
°F 
8.3.5 
SPH 
SetPoint High 
15 
limits high setpoint to 205 
°F 
8.3.6 
OFF1  Actual value correction 
Analog input 1 
8.3.7 
OFF2  Actual value correction 
Analog input 2 
8.3.8 
OFF2  Actual value correction 
Analog input 3 
8.3.9 
Df1 
Digital filter time constant 
Analog input 1 
8.3.10
 
Set parameters
 
 
 See Hint section 2.3, ‘How to adjust parameters’
 
  
The actual value display, (
0
shows the current parameter value
 
The setpoint display, (
AL
shows the parameter item you are adjusting. 
 
Increase 
 or decrease 
 the value,  
accept it by waiting 2 seconds.  
 
Once it flashes, proceed to the next parameter  
(HYSt) by pressing 
 and releasing. 
 
Adjust all of the parameters as shown below. 
 
 
Parameter level values: 
 
Value 
Item 
Description 
 * Sec 
160 
AL 
Limit value for comparator 
8.2 
HYSt  Switching differential for limit comparator 
8.2 
10 
Pb.1 
SPE setpoint external 
9.2 
80 
dt 
Derivative time 
9.2 
350 
rt 
Integral action time 
9.2 
-5 
HYS1  Burner-on 5 
°F below setpoint 
5.5.1 
HYS2  Burner-off, 2-stage 
5.2.3 
HYS3  Burner-off 5 
°F above setpoint 
5.5.1 
Response threshold 
5.6 
Heating curve slope 
5.5.1 
Parallel displacement 
5.5 
 
Set user level values 
 
 
 See Hint section3.4, ‘How to change a setpoint’.
 
 
You may enter the user level, directly from  
the basic display. 
 
Press 
 and release. 
The actual value display, (
180
shows the current user level item value
 
The setpoint display, (
SP 1
shows the user level item you are adjusting. 
 
 
 
Increase 
 or decrease 
 the value, accept it by 
waiting 2 seconds. Once it flashes,  
press 
 and release. 
 
Adjust SP1 as shown below. 
 
User level values: 
 
Value 
Item 
Description 
Sec 
100 
SP 1 
Set point 1 
.5.5.1 
 
 
 
Setup is complete! 
 
 
 
* Sec 
 Refers to the RWF40 user manual section.