Siemens RWF40 Manuel D’Utilisation

Page de 15
13/16                              CC1B-Hints-en 
Preliminary
                                 04.02.2003                                        HVAC Products 
3. Notes
  
3.2 Your record of values 
RWF40 
Setpoint 
Your 
 
 
 
Man. Ref. 
Display 
Setting 
Configuration level items    
( Sec 6.4 )
 
Range 
Factory 
Sec 8.1 
C111 
Analog input 1, 2 and 3;D2 setpoint changeover / shift 
N /A 
9030 
Sec 8.1 / 8.2 
C112 
Limit comparator; controller type; setpoint 1; locking 
N /A 
0010 
Sec 8.1 
C113 
Unit address; decimal place / unit, signal for out-of-range 
N /A 
0110 
 
 
 
 
 
Sec 8.3.1 
SCL 
SC
ale 
L
ow, analog input 1, measured value range 
-1999  to +9999 
Sec 8.3.2 
SCH 
SC
ale 
H
igh, analog input 1, measured value range 
-1999  to +9999 
100 
Sec 8.3.3 
SCL2 
SC
ale 
L
ow, analog input 
2
, measured value range 
-1999  to +9999 
Sec 8.3.4 
SCH2 
SC
ale 
H
igh, analog input 
2
, measured value range 
-1999  to +9999 
100 
 
 
 
 
Sec 8.3.5 
SPL 
S
et 
P
oint 
L
ow limit  
-1999  to +9999 
Sec 8.3.6 
SPH 
S
et 
P
oint 
H
igh limit 
-1999  to +9999 
100 
 
 
 
 
Sec 8.3.7 
OFF1 
OFF
set analog input 
1
, Actual value correction 
-1999  to +9999 
Sec 8.3.8 
OFF2 
OFF
set analog input 
2
, Actual value correction 
-1999  to +9999 
Sec 8.3.9 
OFF3 
OFF
set analog input 
3
, Actual value correction 
-1999  to +9999 
 
 
 
 
Sec 8.3.10 
dF1 
d
igital 
F
ilter, analog input 
1
2
nd
 order, in seconds 
0  to  100 
 
 
 
 
Setpoint 
Your 
 
 
 
Display 
Setting 
Configuration level items
, Modbus option (only RWF40.0X2B97)   
( Sec 6.4 )
 
Range 
Factory 
Sec 8.3.11
 
dF3 
Filter time constant, 
d
igital 
F
ilter, analog input 
3
  weather-dependent setpoint shift 
0  to  1440 
1278 
Sec 8.3.12
 
oLLo 
W
o
rking range,
 L
imit 
Lo
wer 
-1999  to +9999 
-1999 
Sec 8.3.13
 
oLHi 
W
o
rking range,
 L
imit 
Hi
gh 
-1999  to +9999 
9999 
Sec 8.3.14
 
Dtt 
Bus wa
t
ch
D
og 
t
imer (in seconds) 
0  to  7200 
30 
 
 
 
 
 
Setpoint 
Your 
 
 
 
Display 
Setting 
Parameter level items   
( Sec 6.3 )
 
Range 
Factory 
Sec 7 / 8.2 
AL 
A
larm value for K6 
L
imit comparator (alarm programmable relay) 
-1999  to +9999 
Sec 7 / 8.2
 
HYSt 
Hyst
eresis, (switching differential) for K6 limit comparator 
0  to  999.9 
Sec 7 / 8.2
 
Pb.1 
P
roportional 
b
and 
1
 (affects P-response of controller) 
0.1  to   999.9 
10 
Sec 7 / 8.2
 
dt 
d
erivative
 
t
ime (in seconds) (affects D-response of controller) 
0    to   9999 
80 
Sec 7 / 8.2
 
rt  
Integ
r
al action
 
t
ime (in seconds) , (affects I-response of controller) 
0   to   9999 
350 
Sec 7 / 8.2
 
db 
*
 
d
ead 
b
and, contact spacing, * visible when C112 is xxx0, 3-pos modulating 
0  to  999.9 
Sec 7 / 8.2
 
tt 
*
 
Ac
t
uator running
 
t
ime (in seconds) , * visible when C112 is xxx0, 3-pos modulating 
10    to    3000 
15 
Sec 7 / 5.51 
HYS1 
Switch-on threshold, 
HYS
teresis 
1
, 2-stage burner 
0   to   -199.9 
-5 
Sec 7 / 5.2 
HYS2 
Switch-off threshold, 
HYS
teresis 
2
, 2-stage burner 
0  to HYS3 
Sec 7 / 5.2 
HYS3 
Switch-off threshold, 
HYS
teresis 
3
, upper 
0   to   999.9 
Sec 7 / 5.6 
Response threshold (
Q
0   to   999.9 
Sec 7 / 5.51 
H
eating curve slope 
0   to   4 
Sec 7 / 5.5 
P
arallel displacement (weather dependent setpoint shift) 
-90   to   +90 
 
 
 
 
 
Setpoint 
Your 
 
 
 
Display 
Setting 
User level items   
( Sec 6.2.1 )
 
Range 
Factory
Sec 6.2.1 
SP1 
S
et 
P
oint 
1
 
SPL to SPH 
Sec 6.2.1 
SP2 
S
et 
P
oint 
2
, digital input 2, D2=0  
SPL to SPH 
Sec 6.2.1 
dSP 
d
igital 
S
et 
P
oint shift, digital input 2, D2=1  
SPL to SPH 
Sec 11.1.3 
tA 
t
emperature, 
A
mbient (outside) analog input 3, visible when C111 is xx1x, xx2x, xx3x 
 
-- 
Sec 11.1.2 
SP.E 
S
et 
P
oint 
E
xternal, predefinition, analog input 2, visible when C111 is xx1x, xx2x, xx3x 
SPL to SPH 
--