AC-power wiring
BAS-APG001-EN
89
CAUTION
Equipment damage!
Complete input/output wiring before applying power to the EX2 mod-
ule. Failure to do so may cause damage to the module or power trans-
former due to inadvertent connections to power circuits.
CAUTION
Equipment damage!
To prevent module damage, do not share 24 Vac between modules.
Wiring AC-power to the metal-enclosure module
Please read the preceding warnings and cautions. To connect ac-power 
wiring to the enclosure:
1.
Remove the cover of the enclosure.
2.
Remove the knockout for the 0.5 in. (13 mm) conduit from the enclo-
sure and attach the conduit.
3.
Feed the power wire into the enclosure.
4.
When mounting on dry wall or other non-conductive surface, connect 
an earth ground to the earth-ground screw on the enclosure 
(Figure 47 on page 90). 
5.
Connect the ground wire from the 24 Vac transformer (not included) 
to the GND terminal (Figure 47 on page 90).
6.
Connect the power wire to the 24V terminal.
7.
Replace the cover of the enclosure.