18. ADJUSTMENT 
18.4 Time-axis Adjustment of Pens   
 
When the time-axis synchronization (POC) is programmed to “on”, the gaps between the pens may change over 
time, resulting in error between their time-axis. This adjustment is for correction of these changes. It is 
recommended to adjust them once a year for maintaining the time-axis synchronization. 
 
 
Adjustment Flow Chart
 
 
Operation screen 
[Engineering mode selection] 
 
(       +       ) 
   
3 sec. or more
 
 
               
 
[Selecting adjustment] 
 
            → 
 
 
                  
 
 
[Selecting time-axis] 
             
            → 
 
            
 
 
 
[Selecting an adjusting pen] 
 
               
 
 
  (Starting adjustment )
 
 
When (1) the reference pen prints a straight line on 
0% to 100% of the chart and (2) Press        , the 
chart is fed and then the printing of the adjusting pen 
coincides with the straight line (Note) 
Note) If you press        while it does not coincide 
with the straight line, re-execute the procedure 
from the beginning of [Selecting an adjusting 
pen]. 
 
(Computation of 
correction data)
 
 Temporarily storing 
 
Programming other channel? 
 
+ 
Stored  
 
 
 
 
 
 
 
 
 
 
 
Pens stand by at 0% position of scale. 
 
 
 
: Memory clear
 
: Adjustment
 
: Hardware check
 
 
 
 
:  Measured value adjustment
 
:   Shift programming for 
measured value
 
:  Printing position adjustment
 
:   Time-axis adjustment for pens
 
 
 
 
Display
Reference 
pen 
Pen to be 
adjusted 
(1) 1 P
Plotter pen 
1st pen 
(2) 2 P
1st pen 
2nd pen 
(3) 3 P
1st pen 
3rdt pen 
(4) 4 P
1st pen 
4th pen 
 
 
 
Store the computed correction data 
into memory.
Cursor  Adjustment
Cursor 
Time axis
2 sec. or more
Cursor
Other pens than the pen being adjusted
  Adjusting pen selection
DISP
SHIFT
6
A - Z
°C 
 
°F
ENTRY
°C 
 
°F 
ENTRY
°C 
 
°F 
(1) 
(2) (3)
(4)
ENTRY
ENTRY
ENTRY
 
(1) Reference pen 
prints a straight line.
(2) Initial position of the pen adjusted 
Adjustment procedure
(3) When these two 
lines match, press     
                . 
ENTRY
 
Ref. 1 
Ref. 2 
Ref. 3 
Ref. 4 
     
 Engineering mode types
Reference 1
   
Adjustment types 
Reference 2
Reference 3
  Storing 
Reference 4
/
YES 
NO
SHIFT
SET
END