Omega RD200 Manuel D’Utilisation

Page de 134
-75-
 
11. OTHER PROGRAMMING 
11.11 Burnout 
 
The channel where the temperature range is programmed becomes effective. Press                and 
simultaneously in the operation screen for 3 seconds or more to display the [Burnout] programming screen. This 
programming is necessary for each channel.
 
 
1  
Burnout
 
• If a sensor (thermocouple or resistance 
thermometer) is disconnected, trace printing 
overshoots maximum or minimum limit. 
• The default parameter of burnout is “disable” 
() in all channels. 
 
 
Burnout can be selected for each channel out of 3 
types shown below. 
(Non) 
: Burnout disable 

      (UP    burn) 
: Up scale burnout 
  (down burn) 
Down scale burnout
 
 
2  
Programmed Flow Chart
 
<Example> From burnout “disable” to “up scale burnout” 
 
Operation screen 
[Check] 
 
(       +       ) 
    
3 sec. or more 
    
 
[To be ready for programming] 
 
    
 
[Specifying channel]   
 
 
  
 
[Selecting burnout]   
      
Press several times. 
                 
 
 
 
 
 
Temporarily stored 
 
Programming other channels? 
 
 
 
      + 
Stored 
 
 
 
 
 
 
 
A parallel connection of a 
thermocouple with other instrument 
causes a problem. Select () if 
your recorder uses the thermocouple 
being connected with other 
instrument.   
 
 
 
Even if the burnout is programmed to 
a channel where the voltage range 
(No. 01 to 07) is programmed, this 
programming becomes ineffective 
(burnout disable). 
 
 
 
For the burnout operation (display and 
printing), read Section 10.2. 
 
 
 
Press          or         to change 
channels. The programmed burnout of 
other channels can be checked.   
 
 
 
Store the [temporarily stored] 
parameters into memory. 
(Programming change mark is 
printed.) 
Channel 
Cursor 
YES 
NO 
Cursor 
Cursor
 
Burnout selection menu 
  ” programming on 
   parallel operation
 
SHIFT
 
 
DISP
%
SET
END
2
TAG
/
ENTRY
SHIFT
SET
END
/
 
SHIFT
  Storing 
Reference 3
   
Other channels check 
Reference 2
Remarks 1
  Voltage range is ineffective
Remarks 2
 
 
Burnout operation 
Reference 1
Ref. 2
Ref. 3